GE PLCs & Controllers

GE GE IC200ALG620

PLCs & Controllers

Manufacturer: GE Part Number: GE IC200ALG620

Genuine surplus GE IC200ALG620 VersaMax 4-Channel RTD Analog Input Module — Pt100/1000, Ni, Cu resistance sensors, 16-bit resolution, verified condition, in stock.

Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

Description

What the IC200ALG620 Does in a Mark VI System

The IC200ALG620 is a genuine General Electric board part of the Mark VI Speedtronic platform. It is designed to work in Mark VI and related GE turbine control racks alongside GE Mark VI & VersaMax industrial parts hub and other IS200-series I/O cards. The board mounts in a standard VME rack slot and communicates with the DSPX controller over the ISBus fiber-optic backplane. When this board faults, the affected I/O path can cause loss of measurement visibility or protection-trip capability depending on its role in the cabinet.

Technical Specification Summary

  • Manufacturer: General Electric (Emerson / GE Fanuc Automation)
  • Platform: VersaMax Nano / Micro PLC
  • Product Type: RTD Analog Input Module
  • Number of Channels: 4 (independent)
  • Channel Configuration: 3-wire or 4-wire per channel
  • Supported RTD Types: Pt 25 Ω / Pt 100 Ω / Pt 1000 Ω / Ni 100 Ω / Ni 120 Ω / Cu 10 Ω / Cu 50 Ω / Cu 100 Ω / NiFe 604 Ω
  • Resolution: 16-bit
  • Maximum Lead Resistance: 50 Ω per lead (firmware ≥ v1.11), 5 Ω per lead (firmware < v1.11)
  • Current Draw: 125 mA from 3.3 V bus, 125 mA from 5 V bus
  • Manufacturer Part Number Suffix: -DC (default), -FD (DeviceNet), plus OEM sub-families

Why Genuine Surplus Makes Sense for This GE Board

GE’s Mark VI platform remains widely deployed across gas-fired power generation, industrial gas turbine, and compressor-control applications, yet OEM lead times for legacy IS200 boards can stretch to weeks or longer. Autronexa maintains verified surplus and refurbished stock of the IC200ALG620, with each unit functionally tested against OEM specifications and checked for correct markings, part-number cross-reference, and coating codes. Because this board is in stock, you avoid the downtime of waiting on a factory order. For Simplex or TMR configurations, having a verified spare on the shelf is a practical reliability measure — an unexpected board fault during a startup or overhaul can cost more in lost revenue than the board itself.

Sourcing Checklist Before You Order

Before ordering, confirm that your application matches the board’s configuration. The revision suffix trailing the model number indicates hardware revision and coating — our team cross-references markings and part-number suffixes before shipping. Verify your Mark VI rack type and check the board revision and connector layout against your system documentation. When you contact Autronexa with your part number, we can confirm verified condition and current availability, and our sourcing team can help you determine whether this board is the correct fit for your cabinet.

Related GE IS200 Spares in the Same Family

  • IS200DSPXH1D — sister IS200 board in the same Mark VI rack family, frequently requested as a matching spare
  • IS200VCMIH2BCD — sister IS200 board in the same Mark VI rack family, frequently requested as a matching spare
  • GE Mark VI exciter control hub — full listing of GE IS200 exciter boards and VersaMax I/O modules currently available

Frequently Asked Questions

Does the IC200ALG620 read old 5 Ω lead resistance rules or the new 50 Ω rule?
That depends on firmware version. Firmware release 1.11 changed the maximum allowable lead resistance from the earlier 5 Ω per lead to 50 Ω per lead — a major improvement for long cable runs between the RTD and the module. If your replacement module runs firmware earlier than v1.11, it will still enforce the tight 5 Ω limit and may flag alarm codes RTD 7 or 8. You can check the firmware version from the VersaMax CPU diagnostics screen, and GE provides free firmware updates through its services portal.
Can I mix 3-wire and 4-wire RTDs on the same IC200ALG620?
Yes — each of the four channels is independently configurable. You can mix 3-wire and 4-wire sensors on the same module by setting each channel’s configuration jumper and configuring the module parameters in Proficy Machine Edition. 3-wire gives slightly better accuracy than 4-wire for medium lead lengths (10–30 m), while 4-wire is recommended when lead lengths exceed 30 m, because it virtually eliminates lead-resistance error.

Related & compatible parts

GE

IC755CKW15CDM

Genuine surplus GE IC755CKW15CDM QuickPanel+ 15-inch operator terminal, verified and refurbished with clear lead times from Autronexa.

Quote on request

GE

GE IS200DSCBH1AAA

Genuine surplus GE IS200DSCBH1AAA DIN-rail terminal serial board for Mark VI Speedtronic — 6 channels, panel-mounted, verified condition,…

Quote on request

GE

IC697MDL240

Genuine surplus GE Fanuc IC697MDL240 discrete input module for Series 90-70 — 16 isolated 120 VAC inputs, verified…

Quote on request

News & guides for GE

View all articles

Request a quote for this part

Part number: GE IC200ALG620

We reply within one business day.

GE IC200ALG620 Quote reply within 1 business day