Schneider Electric Circuit Protection

Schneider Electric iC60H 2P C20

Circuit Breaker

Manufacturer: Schneider Electric Part Number: iC60H 2P C20

Genuine surplus iC60H 2P C20 from Schneider Electric: 20A C-curve, 10 kA breaking capacity, verified condition and clear lead times.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Rated current 20A
Poles 2P
Trip curve C (thermal-magnetic, magnetic trip 8×In ±20%)
Breaking capacity 10 kA @ 230/400V (IEC 60898-1)
Rated voltage 400V AC, 125V DC
Operating temperature -35 to 70 °C
Mounting 35 mm DIN rail
Dimensions (H×W×D) 85 × 36 × 78.5 mm
Weight 0.25 kg

Description

The Schneider Electric iC60H 2P C20 is a 20 A, two-pole miniature circuit breaker from the Acti9 iC60 range, built for distribution boards that need reliable C-curve protection at 400 V AC. Maintenance teams and panel builders choose genuine surplus or refurbished units when OEM lead times stretch and a verified replacement is needed quickly.

From Fuse Boards to Acti9: Why This Breaker Still Matters

Industrial protection has moved a long way from rewirable fuses and early thermal devices. Modern panels expect compact, DIN-rail components that combine thermal and magnetic tripping in one housing. The Acti9 iC60 family sits at that point in the evolution: a 35 mm DIN rail breaker that fits standard enclosures without adapters. This two-pole variant carries a 20 A rating and a C trip curve, with magnetic trip set at 8×In ±20% — the profile commonly used where modest inrush currents appear on lighting, socket, and small motor circuits. Its 10 kA breaking capacity at 230/400 V under IEC 60898-1 gives panel designers a defined short-circuit rating to work with. The 85 × 36 × 78.5 mm body and 0.25 kg weight keep replacement straightforward in existing rows.

Figure 1: Front view of the Schneider Electric iC60H 2P C20 Circuit Breaker showing its physical design and enclosure.

Reading the Ratings: Current, Curve, and Endurance

Three figures matter most when specifying this unit. First, the 20 A rated current and 2P configuration — both poles switch, which suits single-phase circuits that need a neutral broken alongside the live conductor. Second, the C curve: thermal-magnetic operation with a magnetic trip at 8×In ±20% means the breaker tolerates brief surges while still clearing faults. Third, endurance: 20,000 mechanical cycles and 10,000 electrical cycles define how long the mechanism is expected to operate under test conditions. The rated voltage covers 400 V AC and 125 V DC, and the operating temperature range of -35 to 70 °C covers most industrial cabinet environments. Standards compliance is stated as EN/IEC 60898-1 and EN/IEC 60947-2.

Figure 2: Technical layout and connection details for the Schneider Electric iC60H 2P C20 Circuit Breaker.

Sourcing Genuine Surplus Without the OEM Wait

Because the Acti9 range remains active in production, buyers have options — but OEM channels can still mean quoted lead times that do not match a shutdown window. Autronexa holds genuine surplus and refurbished stock of Schneider Electric components, and every unit is checked against OEM datasheet markings before it ships. For this breaker, that means confirming the 20 A rating, C curve, 2P layout, and 10 kA breaking capacity rather than accepting a lookalike. Refurbished units are tested against OEM datasheet specifications and functionally verified by our sourcing team. If you are matching an existing panel, confirm the exact model string and pole count before ordering, and ask us to verify current lifecycle status and availability. Contact Autronexa with your part number for verified condition and current availability.

📄 Download Datasheet: iC60H 2P C20-datasheet.pdf

Frequently asked questions

Is this iC60H 2P C20 a genuine Schneider Electric breaker, or a copy?

Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference before it is listed. You receive a genuine Schneider Electric breaker, not a grey-market clone.

What condition will the breaker arrive in?

Our default condition is Refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units may also be available — ask for the current condition grade when you enquire.

How fast can you ship the iC60H 2P C20?

Lead time depends on current stock. Contact Autronexa with your part number and we will confirm availability and the shipping window before you order.

Does the 2P configuration break the neutral as well as the live?

Yes — this is a two-pole device, so both poles switch. That suits single-phase circuits where the neutral must be isolated together with the live conductor.

Is the Acti9 iC60 range still supported by Schneider Electric?

The data we hold lists the range as active in production, last verified in 2026-09. Confirm current OEM support status with Autronexa before ordering.

Related & compatible parts

Schneider Electric

140DIO33000C

Genuine surplus Schneider Electric 140DIO33000C intrinsically safe discrete output module — verified condition, ready to ship.

In Stock

Schneider Electric

990NAD23000

Genuine surplus Schneider Electric 990NAD23000 Modbus Plus junction box with screw terminals. Verified condition, ready to ship from…

In Stock

Schneider Electric

TSXPSY5520MC

Genuine surplus Schneider Electric TSXPSY5520MC power supply module for Modicon Premium — verified condition, faster sourcing than OEM…

In Stock

Schneider Electric

TSXCANCADD5

Genuine surplus Schneider Electric TSXCANCADD5 CANopen cordset, 5 m, molded SUB-D9, IP20 — verified condition, ready to ship.

In Stock

News & guides for Schneider Electric

View all articles

Request a quote for this part

Part number: iC60H 2P C20

We reply within one business day.

iC60H 2P C20 Quote reply within 1 business day