Schneider Electric I/O & Function Modules
Schneider Electric 140DDO15310
Output Module Modicon Quantum 32-point TTL 5V DC
Genuine surplus Schneider Electric 140DDO15310 Modicon Quantum 32-point TTL output module — verified condition, tested, and ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Channels | 32 points (4 groups × 8) |
|---|---|
| Signal type | TTL output, 5 V DC, positive logic (sink) |
| Output current | 75 mA per point, 600 mA per group, 2.4 A total |
| Isolation | Group-to-group: 500 Vrms for 1 min |
| Response time | ≤ 250 µs (resistive load) |
| Diagnostics | Blown fuse, loss of field power (LED indication) |
| Supply voltage | 5 V DC (backplane) |
| Bus current | 350 mA @ 5 V DC |
| Power consumption | 4 W |
| Protection rating | IP20 |
| Dimensions (H×W×D) | 250 × 40.34 × 103.85 mm |
| Weight | 0.3 kg |
Description
When a Modicon Quantum rack needs a 32-point TTL output module, the Schneider Electric 140DDO15310 is the genuine part that keeps discrete control loops running. Maintenance teams and integrators choose verified surplus or refurbished units because the series is discontinued, and OEM lead times for remaining stock are unpredictable. Autronexa supplies tested, traceable modules with practical sourcing support.
What This Module Does in a Quantum Rack
The 140DDO15310 is a single-slot discrete output module for the Modicon Quantum platform. It provides 32 TTL output points arranged in four groups of eight, with positive-logic sink behavior and a 5 V DC signal level. Each point handles up to 75 mA, each group up to 600 mA, and the module total is 2.4 A. Group-to-group isolation is rated at 500 Vrms for one minute, which helps contain fault propagation between output groups. Response time is ≤ 250 µs into a resistive load, so the module suits fast discrete signaling rather than high-power switching. Front-panel LEDs report blown fuse and loss of field power, giving technicians a first-line diagnostic before they reach for a meter.

Why Surplus and Refurbished Makes Sense Here
Schneider Electric lists this module as discontinued (end of sale), last verified in 2026-09. That changes the sourcing equation: new-from-OEM channels are closing, and the practical priority becomes finding genuine units in known condition. Autronexa stocks surplus and refurbished Quantum modules and verifies each unit against OEM datasheet markings and part-number cross-reference before it ships. Refurbished units are tested against OEM datasheet specifications and functionally verified by our sourcing team. For a running line, that means a shorter path to a replacement than waiting on an end-of-sale allocation — and a lower cost than the last published list price. If your rack is still in service, keeping a verified spare on the shelf is the practical move.

Sourcing Checklist Before You Order
Confirm the exact model string on your existing module and match it to unit — Quantum I/O part numbers differ by signal type and point count, and a TTL module will not substitute for a relay or triac output. Check that your application actually needs 5 V DC TTL sink outputs and stays within the 75 mA per-point and 2.4 A total limits. Note the 250 × 40.34 × 103.85 mm housing and 0.3 kg weight if you are planning panel space, and respect the IP20 rating by keeping the module in a clean, protected enclosure. Ask your supplier to state condition clearly — surplus, refurbished, or new — and to confirm the unit is genuine. Autronexa provides that verification as standard. Please verify current lifecycle status and availability with Autronexa before ordering.
Frequently asked questions
Is this a genuine Schneider Electric 140DDO15310, or a clone?
Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference before shipping. We supply genuine surplus and refurbished modules, not grey-market copies.
What condition will the module arrive in?
The site default condition is Refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact Autronexa if you need a surplus unit instead.
How fast can you ship the 140DDO15310?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability.
Is the 140DDO15310 still supported by Schneider Electric?
The data lists this module as discontinued (end of sale), last verified 2026-09. Contact Autronexa to confirm OEM support status and remaining stock.
Can this module replace a different Quantum output module?
No. The 140DDO15310 is a 32-point TTL 5 V DC sink output module. Match the exact model string before ordering, because Quantum output modules differ by signal type and point count.
Related & compatible parts
Schneider Electric
ATV71HD30N4
Genuine surplus Schneider ATV71HD30N4 30 kW variable speed drive — verified condition, practical sourcing support, ready to ship.
Schneider Electric
TM218LDA24DRHN
Genuine surplus Schneider Modicon M218 controller, 24 I/O with relay outputs and Ethernet — verified condition, ready to…
Schneider Electric
NWBP85002
Genuine surplus NWBP85002 Modbus Plus bridge for Modicon Premium/Quantum — verified condition, faster than OEM lead time.
Schneider Electric
ATV930U75N4Z
Genuine surplus ATV930U75N4Z variable speed drive from Schneider Electric — verified condition, faster lead time than OEM.
News & guides for Schneider Electric
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Schneider Electric at Datacenter Korea 2026 and Tech Show Madrid: The Integrated AI Data Center Stack
Schneider Electric is pitching an integrated AI data center stack — power, cooling, and software as one system — at…
Schneider Electric spare parts: buying guide, series overview and how to order
Schneider Electric spare parts buying guide: 8 parts online, popular series, condition options and how our RFQ process works.
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
EPC’s New 100 V GaN Inverter Boards: 35 ARMS, 100 kHz, 80 V Bus
In short: On 27 October 2026 EPC announced the EPC91124 and EPC91125, two 100 V three-phase BLDC inverter evaluation boards…
Omron C6 Servo Launches in Europe: What Changes for 1S and Spares
Omron's C6 servo launched in Europe on 7 October 2026 with a 26-bit encoder, 3.5 kHz response and STO. What…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…