Schneider Electric Drives & Inverters
Schneider Electric ATV610D55N4
Variable speed drive
Genuine surplus Schneider Electric ATV610D55N4 drive, 55 kW, 380...460 V, C3 EMC filter — verified condition, ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Rated motor power | 55 kW (75 HP) normal duty; 45 kW (60 HP) heavy duty |
|---|---|
| Supply voltage | 380...460 V AC, 50/60 Hz, three-phase |
| Maximum continuous output current | 120 A (normal duty) |
| Maximum transient current (60 s) | 132 A (normal duty) |
| Dimensions (H×W×D) | 762 × 290 × 323 mm |
| Weight | 53 kg (117 lb), without packaging |
| Protection rating | IP20 (IP40 on the top of the product) |
| Operating temperature | -15...+45 °C without derating; up to +60 °C with power derating |
| Integrated HMI | Plain text display terminal VW3A1113 (2 lines, white backlit LCD, RJ45) |
| Integrated EMC filter | Category C3 EMC filter |
Description
When a 55 kW pump or fan drive fails on a running process, every hour of downtime adds cost. The Schneider Electric ATV610D55N4 is a genuine Easy Altivar 610 variable speed drive rated 55 kW (75 HP) normal duty and 45 kW (60 HP) heavy duty on a 380…460 V three-phase supply. Autronexa supplies verified surplus and refurbished units so maintenance teams can restore operation without waiting on OEM lead times.
What This Drive Does in a Pump or Fan System
The Easy Altivar 610 family is built for variable-torque pump and fan duty, and this frame size 5 unit carries an integrated C3 EMC filter and a plain text display terminal VW3A1113 with a two-line white backlit LCD and RJ45 connection. Control modes cover U/f Vc Standard, 5-point, and Quadratic, plus open-loop synchronous motor control and reluctance motor control. Six 24 V DC digital inputs (two programmable as pulse inputs), three analog inputs configurable for 0…10 V or 0…20 mA, two analog outputs, and three relay outputs give the I/O needed for pressure, flow, or temperature feedback. Slot A accepts an Extended I/O module VW3A3203 or Extended relay module VW3A3204 when more points are required.

Technical Specs That Matter on Site
Three values shape installation planning. First, the maximum continuous output current is 120 A normal duty with 132 A transient for 60 s, while heavy duty is 88 A continuous and 132 A transient. Second, the drive measures 762 × 290 × 323 mm and weighs 53 kg without packaging, so confirm cabinet space and lifting arrangements before delivery. Third, the fan is field-replaceable in under five minutes without special tools, which shortens planned maintenance. Power terminal tightening torque is 25 N·m on frame 5. The drive is IP20 rated (IP40 on top), operates from -15…+45 °C without derating, and carries CE marking and CSA C22.2 No. 274 certification. Built-in Modbus RTU runs over two RJ45 ports, and Slot A accepts a PROFIBUS DP V1 module VW3A3607 if required.

Why Genuine Surplus Fits This Model
A 55 kW drive is a capital item, and OEM lead times can stall a repair schedule. Autronexa stocks genuine surplus and refurbished Easy Altivar 610 units that are tested against OEM datasheet specifications and functionally verified by our sourcing team. Because the product line remains current, refurbished stock offers a practical alternative to full list price without the uncertainty of grey-market clones. Every unit is checked for model and revision match before dispatch, and our engineers can confirm accessory compatibility for Slot A modules and the VW3A1113 terminal. Please verify current lifecycle status and availability with Autronexa before ordering. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this ATV610D55N4 a genuine Schneider Electric drive or a clone?
Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference before listing. We supply genuine surplus and refurbished Schneider Electric drives, not grey-market copies.
What condition will the drive arrive in?
Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact Autronexa if you need a specific condition grade confirmed before purchase.
How fast can you ship the ATV610D55N4?
Lead time depends on current stock. Contact Autronexa for current lead time and availability; surplus and refurbished units are ready to ship once verified.
Does this drive support Modbus and PROFIBUS?
Built-in communication is Modbus RTU over two RJ45 ports. PROFIBUS DP V1 is supported through the optional VW3A3607 module in Slot A.
Is the Easy Altivar 610 line still supported by Schneider Electric?
Official product pages for the Easy Altivar 610 line were active as of 2026-10. Contact Autronexa to verify OEM support status for your specific revision.
Related & compatible parts
Schneider Electric
ATV610C40N4
Genuine surplus ATV610C40N4 from Schneider Electric: 400 kW normal duty, 380...460 V, Modbus, C3 EMC filter. Verified condition,…
Schneider Electric
ATV610D75N4Z
Genuine surplus Schneider Electric ATV610D75N4Z 75 kW drive — verified condition, faster lead time than OEM, and technical…
Schneider Electric
140CPS21400
Genuine surplus Schneider 140CPS21400 power supply for Modicon Quantum — verified condition, faster lead time than OEM.
Schneider Electric
170ADM39030C
Genuine surplus Schneider Electric 170ADM39030C relay I/O base — 10 inputs, 8 relay outputs, verified and ready to…
News & guides for Schneider Electric
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Schneider Electric at Datacenter Korea 2026 and Tech Show Madrid: The Integrated AI Data Center Stack
Schneider Electric is pitching an integrated AI data center stack — power, cooling, and software as one system — at…
Schneider Electric spare parts: buying guide, series overview and how to order
Schneider Electric spare parts buying guide: 8 parts online, popular series, condition options and how our RFQ process works.
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
EPC’s New 100 V GaN Inverter Boards: 35 ARMS, 100 kHz, 80 V Bus
In short: On 27 October 2026 EPC announced the EPC91124 and EPC91125, two 100 V three-phase BLDC inverter evaluation boards…
Omron C6 Servo Launches in Europe: What Changes for 1S and Spares
Omron's C6 servo launched in Europe on 7 October 2026 with a 26-bit encoder, 3.5 kHz response and STO. What…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…