Technical specifications

Number of Outputs 8
Output Ranges 0...20 mA, 0...25 mA, 4...20 mA
Accuracy ±0.2% of full scale at 25°C
Maximum Loop Resistance 500 Ohm
Update Time 4 ms
Setting Time 1 ms to ±0.1% of final value
Power Dissipation 12.5 W
Bus Current Requirement 2.5 A
Operating Temperature 0...60 °C
Marking CE, II1 G/D-EEx ia IIC

Description

The Schneider Electric 140AIO33000 is an intrinsically safe analog output module from the Modicon Quantum series, built for control systems in hazardous zones. Maintenance and procurement teams choose genuine surplus or refurbished units to avoid OEM lead times while keeping verified authenticity and clear condition reporting. Autronexa supplies this module with practical sourcing support and current availability confirmed before order.

What This Module Does in a Quantum System

The module provides eight analog output channels for the Modicon Quantum automation platform. It supports 0…20 mA, 0…25 mA and 4…20 mA output ranges, with 4…20 mA available at 15-bit resolution. Accuracy is ±0.2% of full scale at 25°C, and linearity stays within ±1 LSB. An update time of 4 ms and a setting time of 1 ms to ±0.1% of final value suit control loops that need repeatable response. An internal fuse protects the module, and isolation between channels and bus is rated 1780 Vrms for 60 s AC. The unit is marked CE and II1 G/D-EEx ia IIC, with hazardous-location certifications including Class 1, Division 1 groups A, B, C and SIRA 02ATEX2345X. Hot swapping is not allowed per intrinsic safety standards.

Figure 1: Front view of the Schneider Electric 140AIO33000 Intrinsically Safe Analog Output Module showing its physical design and enclosure.

Surplus Advantage for This Safety-Rated Module

Intrinsically safe modules often carry long OEM lead times because they sit in a specialised certification category. Genuine surplus and professionally refurbished units give maintenance teams a practical alternative. Autronexa verifies each module against OEM datasheet markings and part-number cross-reference, then functionally checks it before dispatch. Refurbished units are tested against OEM datasheet specifications and functionally verified by our sourcing team. For this model, the relevant checks include the eight output channels, the ±0.2% accuracy at 25°C, the 500 Ohm maximum loop resistance and the internal fuse. Because the module carries hazardous-area markings, buyers should confirm the exact certification suffix and revision match their existing installation before ordering.

Figure 2: Technical layout and connection details for the Schneider Electric 140AIO33000 Intrinsically Safe Analog Output Module.

Sourcing Checks Before You Order

Confirm the exact model and any revision notes on your existing module, then match the certification marking to your hazardous-zone classification. Decide whether your application needs surplus, refurbished or another condition grade, and verify that the 4…20 mA range and 15-bit resolution fit your loop requirements. The module operates from 0…60 °C ambient and stores from -40…85 °C, with 95% relative humidity without condensation. Please verify current lifecycle status and availability with Autronexa before ordering. Contact Autronexa with your part number for verified condition and current availability.

Frequently asked questions

Is this a genuine Schneider Electric 140AIO33000, or a clone?

Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference. The module carries the CE and II1 G/D-EEx ia IIC markings stated in the datasheet, and we confirm these before dispatch.

What condition will the 140AIO33000 arrive in?

Our default condition is refurbished, tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available depending on stock. Contact Autronexa for the current condition grade of this specific module.

How fast can you ship the 140AIO33000?

Lead time depends on current stock and condition grade. Contact Autronexa for current lead time and availability before placing your order.

Does this module work with Modicon Quantum systems?

Yes, it is part of the Modicon Quantum automation platform and supports Concept V2.2 and above, ProWORX and Unity Pro software designations. Confirm your exact system revision with Autronexa before ordering.

Is the 140AIO33000 still supported by Schneider Electric?

Lifecycle status is not stated in our datasheet data. Contact Autronexa to verify OEM support status and current availability.

Related & compatible parts

Schneider Electric

BMEP584040S

Genuine surplus BMEP584040S safety processor — verified, tested, and ready to ship from Autronexa.

In Stock

Schneider Electric

BMENUA0100

Genuine surplus Schneider Electric BMENUA0100 serial module for Modicon M580 — verified condition, practical lead times, and sourcing…

In Stock

Schneider Electric

140DDI84100

Genuine surplus Schneider Electric 140DDI84100 Modicon Quantum 16-point DC input module — verified, tested, and ready to ship…

In Stock

Schneider Electric

BMXRMS128MPF

Genuine surplus Schneider Electric BMXRMS128MPF 128MB SD flash memory card for Modicon M340 processors — verified condition, ready…

In Stock

News & guides for Schneider Electric

View all articles

Request a quote for this part

Part number: 140AIO33000

We reply within one business day.

140AIO33000 Quote reply within 1 business day