ABB DI840
Cable length 600 meters
Genuine surplus ABB DI840 digital input module: 16 channels, 24 V d.c., SOE, redundant-ready. Verified condition and current availability from Autronexa.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Input voltage range, "0" | -30..+5 V |
|---|---|
| Input voltage range, "1" | 11..30 V |
| Number of channels | 16 |
| Signal type | Current sinking |
| Isolation | Groupwise isolated from ground |
| Maximum field cable length | 600 meters (656 yards) |
| Event recording resolution | 1 ms |
| Operating temperature | 0 to +55 °C (+32 to +131 °F) |
| Protection class | IP20 according to IEC 60529 |
Description
When a digital input module fails on a running S800 I/O station, every hour of downtime adds cost. The ABB DI840 is a 16-channel, 24 V d.c. digital input module for single or redundant applications, and sourcing a genuine surplus or refurbished unit from Autronexa gets your system back online without the OEM lead time.
What the DI840 Does in an S800 System
This unit handles 16 current-sinking digital inputs, grouped as one set of 16 isolated from ground. Each channel includes current-limiting components, EMC protection, an input state LED, and an optical isolation barrier. The module supervises transducer power and limits current, with one output per two input channels. For maintenance engineers, the front LEDs (Fault, Run, Warning, and Channel 1–16 Status) make fault finding straightforward: a channel-level fault is visible without pulling the module. The on-board diagnostics also supervise process power and internal circuitry, reporting module error, module warning, and channel error status. The Sequence of Events (SOE) function records events at 1 ms resolution with an event queue of up to 257 entries, and a shutter filter removes unwanted events. This makes the module useful where you need to reconstruct the order of trips or interlocks after a shutdown.

Technical Specs That Matter on the Floor
Three specifications drive most maintenance decisions on this module. First, the input voltage range: a “0” is -30 to +5 V and a “1” is 11 to 30 V, so the module tolerates the voltage sag and offset common on long field circuits. Second, the maximum field cable length is 600 meters (656 yards), which supports large plant layouts without intermediate repeaters. Third, the module is groupwise isolated from ground with a rated insulation voltage of 50 V and a dielectric test voltage of 500 V a.c., protecting the backplane from field-side transients. The module draws 100 mA from the +5 V Modulebus and 15 mA from +24 V external, plus transducer power up to a maximum of 335 mA. Power dissipation is typically 2.7 W. Operating temperature is 0 to +55 °C, with approvals issued for +5 to +55 °C; for vertical mounting in a compact MTU, maximum ambient is 40 °C. The IP20 rating suits cabinet installation, and corrosion protection meets ISA-S71.04: G3.
Surplus Advantage and Sourcing Guidance
ABB S800 I/O remains widely installed, but lead times on new modules can stretch when a single channel fails. Autronexa stocks genuine surplus and refurbished unit units that are tested against OEM datasheet specifications and functionally verified by our sourcing team. That means you get a module with confirmed channel operation, LED function, and communication integrity, not an untested pull. Before ordering, confirm three things: the exact article number (3BSE020836R1), the MTU you will pair it with (This unit is compatible with TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU842, TU843, and TU852), and the keying code CD. If your application requires redundancy, the module supports it; if you need SOE, confirm your controller configuration accepts the event queue. Contact Autronexa with your part number for verified condition and current availability. Please verify current lifecycle status and availability with Autronexa before ordering.
Frequently asked questions
Is this a genuine ABB DI840, or a clone?
Autronexa verifies every unit against OEM datasheet markings and part-number cross-reference. We supply genuine surplus and refurbished ABB modules, not grey-market copies.
What condition will the DI840 arrive in?
Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available; condition is confirmed at quote.
How fast can you ship the DI840?
Lead time depends on current stock. Contact Autronexa for current lead time and availability; surplus and refurbished units are often ready to ship faster than OEM factory orders.
Which MTUs work with the DI840?
The module is compatible with TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU842, TU843, and TU852. Confirm your MTU and keying code CD before installation.
Does the DI840 support redundant applications?
Yes. The DI840 supports single or redundant configurations, and the SOE function records events at 1 ms resolution with a 257-event queue.
Related & compatible parts
ABB
TB825
Genuine surplus ABB TB825 ModuleBus optical media converter — verified, tested, and ready to ship for S800 I/O…
ABB
DI524
Genuine surplus ABB DI524 S500 digital input module — 32 DI at 24VDC, verified condition and faster lead…
ABB
AI830A
Genuine surplus ABB AI830A RTD input module — 8 channels, 3-wire, S800 mechanics. Verified condition, faster than OEM…
ABB
07 SL 97
Genuine surplus ABB 07 SL 97 central unit processor with CS 31 field bus, 480 kByte Flash EPROM/RAM…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…