Schneider Electric Drives & Inverters

Schneider Electric ATV610D90N4

Variable speed drive

Manufacturer: Schneider Electric Part Number: ATV610D90N4

Genuine surplus ATV610D90N4 drive: 90 kW normal duty, 380...460 V three-phase, C3 EMC filter, Modbus RTU — verified and ready to ship.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Rated motor power 90 kW (125 HP) normal duty; 75 kW (100 HP) heavy duty
Supply voltage 380...460 V AC, 50/60 Hz, three-phase
Maximum continuous output current 173 A (normal duty)
Maximum transient current (60 s) 190 A (normal duty)
Integrated EMC filter Category C3
Integrated HMI Plain text display terminal VW3A1113 (2 lines, white backlit LCD, RJ45)
Digital inputs 6, 24 V DC (2 can be programmed as pulse inputs)
Analog outputs 2, software-configurable 0...10 V / 0...20 mA
Operating temperature -15...+45 °C without derating; up to +60 °C with power derating
Dimensions (H×W×D) 762 × 290 × 323 mm

Description

The ATV610D90N4 is a Schneider Electric Easy Altivar 610 variable speed drive rated 90 kW (125 HP) normal duty on a 380…460 V three-phase supply. Maintenance teams choose genuine surplus or refurbished units of this model to replace failed drives without waiting on OEM lead times, while keeping the integrated C3 EMC filter and plain text terminal VW3A1113 they already rely on.

What This Drive Does on the Plant Floor

This is a fan-and-pump drive first. Its quadratic U/f control mode (UFQ) matches variable-torque loads, and the 90 kW normal-duty rating covers the larger air-handling and water-circulation duties where a drive failure stops the whole process. The frame 5 chassis measures 762 × 290 × 323 mm and weighs 53 kg without packaging, so plan lifting and panel space accordingly. The integrated C3 EMC filter removes one external component from the enclosure, and the VW3A1113 plain text terminal gives two lines of backlit LCD for local diagnostics without a laptop. Six 24 V DC digital inputs, three analog inputs and two analog outputs cover typical pump and fan feedback and control signals. Slot A accepts the VW3A3203 extended I/O or VW3A3204 extended relay module if the application needs more points.

Figure 1: Front view of the Schneider Electric ATV610D90N4 Variable speed drive showing its physical design and enclosure.

Serviceability and Reliability Details

For maintenance engineers, the practical details matter more than the headline rating. The cooling fan is field-replaceable in under 5 minutes without special tools, which turns a common wear item into a short planned stop rather than a long outage. Electronic cards carry a protective conformal coating, and the drive is rated for 3C3/3S3 chemical and mechanical conditions per IEC/EN 60721, so it tolerates the dust and humidity found in many pump rooms and air-handling spaces. Operating temperature is -15…+45 °C without derating, extending to +60 °C with power derating. The drive accepts 150 m shielded or 200 m unshielded motor cable without a dv/dt output filter, and Schneider recommends an output filter above 50 m. Power terminal tightening torque for frame 5 is 25 N·m. Built-in Modbus RTU over RJ45 supports integration with the plant network; wiring into other fieldbuses may require an external gateway or option module, so confirm cables and gateways with your supplier.

Figure 2: Technical layout and connection details for the Schneider Electric ATV610D90N4 Variable speed drive.

Why Genuine Surplus Fits This Model

Autronexa supplies genuine surplus and professionally refurbished automation components, and this drive is the kind of unit our sourcing team handles regularly. Refurbished units are tested against OEM datasheet specifications and functionally verified before they ship. That matters when a 90 kW drive is the single point of failure for a process fan: a verified surplus unit can often be dispatched faster than a factory order, and at a lower cost than OEM list price. The Easy Altivar 610 line remains current, so lifecycle support is not the issue — availability and lead time usually are. Please verify current lifecycle status and availability with Autronexa before ordering. Contact Autronexa with your part number for verified condition and current availability.

📄 Download Datasheet: ATV610D90N4-datasheet.pdf

Frequently asked questions

Is this a genuine Schneider Electric ATV610D90N4, or a clone?

Autronexa verifies every unit against OEM datasheet markings and part-number cross-reference before it enters stock. We supply genuine surplus and refurbished components only, not grey-market copies.

What condition will the drive arrive in?

Our default condition is Refurbished: the unit is tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact Autronexa if you need a surplus unit in as-removed condition instead.

How fast can you ship the ATV610D90N4?

Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability; we confirm dispatch timing before you order.

Does this drive work with our existing Modbus network?

Yes — the unit has two built-in RJ45 ports, one for Modbus field network and one for HMI multidrop, supporting Modbus RTU. For PROFIBUS DP, Slot A accepts the VW3A3607 module. Confirm your network architecture with our sourcing team.

Is the Easy Altivar 610 line still supported by Schneider Electric?

Schneider Electric's official product pages for the Easy Altivar 610 line were active as of 2026-10. Contact Autronexa to verify current OEM support status for your specific unit.

Related & compatible parts

Schneider Electric

ABE7H16R21

Genuine surplus Schneider Electric ABE7H16R21 16-channel sub-base, verified and ready to ship from Autronexa.

In Stock

Schneider Electric

TWDLCAA40DRF

Genuine surplus Schneider TWDLCAA40DRF compact base controller — 40 discrete I/O, verified condition, ready to ship from Autronexa.

In Stock

Schneider Electric

ABFC08R02B

Genuine surplus Schneider Electric ABFC08R02B commoning link for Modicon Momentum — verified condition, ready to ship from Autronexa.

In Stock

Schneider Electric

BMXCPS2000

Genuine surplus Schneider Electric BMXCPS2000 power supply module for Modicon X80 — verified condition, practical lead times.

In Stock

News & guides for Schneider Electric

View all articles

Request a quote for this part

Part number: ATV610D90N4

We reply within one business day.

ATV610D90N4 Quote reply within 1 business day