Schneider Electric I/O & Function Modules

Schneider Electric 140ATI03000

Analogue input module

Manufacturer: Schneider Electric Part Number: 140ATI03000

Genuine surplus Schneider 140ATI03000: 8-channel thermocouple input for Modicon Quantum, verified and ready to ship.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Analogue input number 8
Analogue input type Thermocouple J, K, E, T, R, S
Analogue input resolution 16 bits
Update time 1000 ms
Isolation between channels and bus 1780 V AC 60 s / 2500 V DC 60 s
Bus current requirement 280 mA
Power dissipation 1.5 W
Net weight 0.7 lb(US) (0.3 kg)

Description

When a thermocouple input module fails on a running Modicon Quantum system, unplanned downtime compounds hour by hour. Sourcing a genuine Schneider Electric 140ATI03000 fast matters. This 8-channel analogue input module reads J, K, E, T, R and S thermocouples with 16-bit resolution, and Autronexa supplies it as verified surplus or refurbished stock — tested against OEM datasheet specifications and functionally verified by our sourcing team.

What This Module Does in a Quantum Rack

The 140ATI03000 is an analogue input module from the Modicon Quantum automation platform. It accepts eight thermocouple inputs and converts them to 10 input words for the Quantum backplane. On-board cold junction compensation covers 32…140 °F (0…60 °C), so the module handles reference-junction correction internally rather than relying on external hardware. Two filters are built in: a notch filter at 3 dB for 50/60 Hz and a single-pole low-pass filter at 3 dB for 20 Hz. The update time is 1000 ms across all channels. Front-panel LEDs report bus communication, external faults, and per-channel on/fault status, which shortens troubleshooting during a hot swap.

Figure 1: Front view of the Schneider Electric 140ATI03000 Analogue input module showing its physical design and enclosure.

Why Surplus Makes Sense for This Part

OEM lead times on Quantum I/O modules can stretch well beyond a planned maintenance window. Autronexa keeps genuine surplus and refurbished units of this analogue input module in rotation because it is a regularly requested part in the Quantum family. Each unit is checked against OEM datasheet markings and part-number cross-reference before it ships. Refurbished stock is tested against OEM datasheet specifications and functionally verified by our sourcing team — not just powered up. For plants holding a spare Quantum rack, this is a practical way to keep a verified spare on the shelf without paying full OEM list price. Please verify current lifecycle status and availability with Autronexa before ordering.

Figure 2: Technical layout and connection details for the Schneider Electric 140ATI03000 Analogue input module.

Selection and Sourcing Notes

Before you order, confirm the exact model and any revision suffix on your existing module, because Quantum racks can mix I/O types and the slot addressing must match. Decide whether you need surplus (pulled from service, untested beyond visual) or refurbished (functionally verified) — Autronexa will state the condition of each unit clearly. Check that your field wiring matches the thermocouple types you actually run: this module supports J, K, E, T, R and S ranges, and accuracy differs by type, from ±2 °C plus 0.1 % of reading on J, K, E and T to ±4 °C plus 0.1 % of reading on R and S. Also verify the cold junction compensation range suits your cabinet ambient. Contact Autronexa with your part number for verified condition and current availability.

Frequently asked questions

Is this a genuine Schneider Electric 140ATI03000, or a clone?

Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference before it ships. We supply genuine surplus and refurbished modules, not grey-market copies.

What condition will the module arrive in?

Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available and clearly labelled. Contact Autronexa to confirm the condition of current stock.

How fast can you ship the 140ATI03000?

Lead time depends on current stock. Contact Autronexa for current lead time and availability — we will confirm before you commit.

Which thermocouple types does this module accept?

It supports J, K, E, T, R and S thermocouples with 16-bit resolution. Accuracy is ±2 °C plus 0.1 % of reading for J, K, E and T, and ±4 °C plus 0.1 % of reading for R and S.

Is the 140ATI03000 still supported by Schneider Electric?

Lifecycle status is not stated in our data. Contact Autronexa to verify OEM support status and current availability before ordering.

Related & compatible parts

Schneider Electric

140DDO36400C

Genuine surplus Schneider 140DDO36400C DC output module for Modicon Quantum — verified, tested, and ready to ship.

In Stock

Schneider Electric

iC60N 1P C10

Genuine surplus Schneider Electric iC60N 1P C10 10A C-curve MCB, 6 kA — verified condition, faster than OEM…

In Stock

Schneider Electric

ATV930C11N4

Genuine surplus Schneider Electric ATV930C11N4 drive — 110 kW ND/90 kW HD, dual-rated, built-in braking unit. Verified condition,…

In Stock

Schneider Electric

ABE7H16S43

Genuine surplus Schneider Electric ABE7H16S43 16-channel input sub-base — verified condition, faster lead time than OEM.

In Stock

News & guides for Schneider Electric

View all articles

Request a quote for this part

Part number: 140ATI03000

We reply within one business day.

140ATI03000 Quote reply within 1 business day