Schneider Electric Circuit Protection

Schneider Electric iC60N 2P C16

Circuit Breaker

Manufacturer: Schneider Electric Part Number: iC60N 2P C16

Genuine Schneider iC60N 2P C16 circuit breaker — verified surplus/refurbished, 16A C-curve, 6 kA, ready to ship.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Poles 2P
Rated current 16A
Trip curve C (thermal-magnetic, magnetic trip 8×In ±20%)
Breaking capacity 6 kA @ 230/400V (IEC 60898-1)
Rated voltage 400V AC, 125V DC
Standard EN/IEC 60898-1, EN/IEC 60947-2
Operating temperature -35 to 70 °C
Mounting 35 mm DIN rail
Mechanical / electrical life 20,000 / 10,000 cycles
Dimensions (H×W×D) 85 × 36 × 78.5 mm

Description

When a 16 A final circuit trips and will not reset, the cause is often a tired breaker rather than the load. The Schneider Electric iC60N 2P C16 miniature circuit breaker restores dependable two-pole protection, and Autronexa supplies it as a verified genuine unit with faster availability than a factory order.

What This Acti9 iC60N Breaker Does in Service

The iC60N sits in the Acti9 iC60 family and protects two-pole final circuits against overload and short circuit. Its C-curve thermal-magnetic trip releases magnetically at 8×In ±20%, so it tolerates brief inrush from small motors and transformers without nuisance tripping. Rated current is 16A, breaking capacity is 6 kA at 230/400V under IEC 60898-1, and the unit accepts 400V AC or 125V DC. The 36 mm width and 35 mm DIN rail mounting make like-for-like replacement straightforward during a maintenance window, and the 20,000 mechanical / 10,000 electrical cycle ratings give a clear basis for judging a used unit’s remaining life.

Figure 1: Front view of the Schneider Electric iC60N 2P C16 Circuit Breaker showing its physical design and enclosure.

Why Genuine Surplus Fits This Breaker

Because the Acti9 range is listed as active in production, buyers sometimes assume only a new distributor order will do. In practice, verified surplus and refurbished stock often reaches a maintenance team sooner. Every unit we offer is checked against OEM datasheet markings and functionally verified by our sourcing team before dispatch; refurbished breakers are tested against OEM datasheet specifications. For a device this compact and this widely installed, that means you can keep a spare on the shelf without paying full list price — genuine parts, verified.

Sourcing Checks Before You Order

Confirm the pole count, rated current and trip curve match the failed device: 2P, 16A, C-curve. Check the DIN rail clip and terminal condition on arrival, and record the mechanical and electrical cycle history where known. Decide whether surplus or refurbished condition suits the duty — for critical final circuits, a refurbished unit with documented verification is the practical choice. Please verify current lifecycle status and availability with Autronexa before ordering, and contact us with your part number for verified condition and current availability.

📄 Download Datasheet: iC60N 2P C16-datasheet.pdf

Frequently asked questions

Is this a genuine Schneider Electric iC60N 2P C16, or a copy?

Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference before it is listed. We supply genuine surplus and refurbished components, not grey-market clones.

What condition will the breaker arrive in?

Our default condition is Refurbished: the unit is tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available — state your preference when you enquire.

How fast can you ship the iC60N 2P C16?

Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability; surplus and refurbished stock is ready to ship once confirmed.

Does this breaker suit a 400V AC two-pole circuit?

Yes — the datasheet rates it at 400V AC and 125V DC, with 2 poles, 16A rated current and 6 kA breaking capacity at 230/400V to IEC 60898-1.

Is the Acti9 iC60 range still supported by Schneider Electric?

The datasheet lists the lifecycle as Active (in production, Acti9 range), last verified 2026-09. Confirm current support status with Autronexa before ordering.

Related & compatible parts

Schneider Electric

140ARI03010C

Genuine surplus Schneider Electric 140ARI03010C analogue input module — 8 differential inputs, 13-bit resolution, verified condition and ready…

In Stock

Schneider Electric

ATV320U75N4WS

Genuine surplus Schneider ATV320U75N4WS: 7.5 kW, IP65 wall-mount drive with disconnect and C2 EMC filter — verified condition,…

In Stock

Schneider Electric

140CHS11000

Genuine surplus Schneider Electric 140CHS11000 hot standby module for Modicon Quantum — verified condition, practical lead times.

In Stock

Schneider Electric

TSXMRPC001M

Genuine surplus Schneider TSXMRPC001M SRAM memory for TSX Micro PLCs — verified condition, 192–1024 kB capacity, ready to…

In Stock

News & guides for Schneider Electric

View all articles

Request a quote for this part

Part number: iC60N 2P C16

We reply within one business day.

iC60N 2P C16 Quote reply within 1 business day