ABB CI865
Module is the AC 800M system’s communication interface
Genuine surplus ABB CI865 module for AC 800M — bridges Satt I/O with hot-swap support. Verified condition, ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Article Number | 3BSE040795R1 |
|---|---|
| Communication Protocol | ABB's Satt I/O |
| Master or Slave | Master |
| Hot Swap | Yes |
| Max Units on CEX Bus | 4 |
| Connector | BNC |
| 24 V Consumption (typ.) | 120 mA |
| Operating Temperature | 0 to +55 °C (+32 to +131 °F) |
| Protection Class | IP20 according to EN60529, IEC 529 |
| Dimensions (W×H×D) | 59 mm × 185 mm × 127.5 mm |
Description
When a legacy Satt I/O segment needs to stay online on an AC 800M controller, the ABB CI865 communication interface module is the bridge that keeps that link alive. Maintenance teams running mixed-generation ABB systems rely on this module to connect older rack-based I/O without replacing the entire controller platform — and genuine surplus stock is often the only practical path to a fast replacement.
What the CI865 Does in an AC 800M System
This unit is not a general-purpose ControlNet interface. Its job is specific: it lets the AC 800M controller communicate with Satt ControlNet and, through that, with older Satt I/O systems — both 19-inch rack I/O and Series 200 I/O. That makes it a targeted migration and sustainment part rather than a universal communication card.
Functionally, the module acts as a master on the Satt I/O bus and handles I/O scanning for up to 31 distributed I/O systems. It supports hot swap, so a failed unit can be replaced online without pre-configuration — a practical detail when every minute of downtime counts. The module uses a BNC connector and draws a typical 120 mA at 24 V. Up to four units can sit on the CEX bus. Note that it cannot be used in a High Integrity controller, so confirm your controller type before ordering.

Technical Specifications at a Glance
This unit carries an IP20 protection class per EN60529 and IEC 529, with corrosion protection rated G3 compliant to ISA 71.04 — relevant for control rooms and cabinets where airborne contaminants are a concern. Operating temperature range is 0 to +55 °C, and storage tolerance spans -40 to +70 °C. The module measures 59 mm wide, 185 mm high, and 127.5 mm deep, weighing 700 g including its base. It is CE-marked and compliant with EU, UAE, and CN RoHS directives as well as WEEE. These are the figures to check against your panel space and environmental envelope before committing a replacement.

Sourcing Genuine unit Modules Without the OEM Wait
Because This unit serves a specific legacy role, new-from-OEM availability can be slow or uncertain. Autronexa stocks genuine surplus and refurbished units that are tested against OEM datasheet specifications and functionally verified by our sourcing team. For a module like this — where a wrong or cloned card can stall a whole I/O segment — verified condition matters more than a glossy box. Refurbished units arrive functionally checked, and surplus stock often ships faster than factory lead times. If you are maintaining an AC 800M system with Satt I/O still in service, contact Autronexa with your part number for verified condition and current availability. Please verify current lifecycle status and availability with Autronexa before ordering.
Frequently asked questions
Is this a genuine ABB CI865, or a clone?
Autronexa verifies every CI865 against OEM datasheet markings and part-number cross-reference. We supply genuine surplus and refurbished units, not grey-market copies.
What condition will the CI865 arrive in?
Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available — confirm the condition you need when you request a quote.
Can the CI865 be used in a High Integrity controller?
No. The CI865 cannot be used in a High Integrity controller. Confirm your controller type before ordering, and contact Autronexa if you need help matching the right module to your AC 800M configuration.
Does the CI865 support hot swap?
Yes. The module supports online replacement (hot swap) and does not require configuration before installation, which helps reduce downtime during maintenance.
How fast can Autronexa ship a CI865?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability — surplus and refurbished units are often ready to ship faster than OEM lead times.
Related & compatible parts
ABB
CI856
Genuine surplus ABB CI856 S100 I/O interface for AC 800M — verified, tested, and ready to ship with…
ABB
DI831
Genuine surplus ABB DI831 16-channel 48 V d.c. digital input module for S800 I/O — verified condition, practical…
ABB
CI540
Genuine surplus ABB CI540 S100 I/O Bus Extension module — verified condition, tested against OEM datasheet specs, ready…
ABB
DI825
Genuine surplus ABB DI825, 8-channel 125 V d.c. digital input for S800 I/O, individually isolated, verified and ready…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…