ABB DP840
Module consists
Genuine surplus ABB DP840 8-channel pulse counter module with 20 kHz frequency measurement and advanced diagnostics — verified and ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Article number | 3BSE028926R1 |
|---|---|
| Signal specification | 24 V d.c. (19.2 - 32 V d.c.) |
| Number of channels | 8 |
| Type | Pulse counter |
| Redundancy | Yes |
| Mechanics | S800 |
| Isolation | Groupwise isolated from ground |
| Maximum field cable length | 200 meters (218 yards) |
| Power dissipation | 4 W |
| Protection class | IP20 according to IEC 60529 |
Description
When pulse and frequency signals from field transducers must be counted reliably, the ABB DP840 8-channel pulse counter module delivers verified performance for S800 systems. Maintenance and procurement teams choose genuine surplus or refurbished units to avoid OEM lead times while keeping signal integrity intact.
What the DP840 Module Does in an S800 System
This unit module consists of eight identical independent channels. Each channel can be configured for pulse count or frequency (speed) measurement up to 20 kHz, and the inputs can also be read as DI signals. A configurable input filter on every channel helps reject noise from long field cables. The module performs self-diagnostics cyclically, and advanced diagnostics support both single and redundant applications. An interface for NAMUR, 12 V and 24 V transducer signal levels lets the same module serve multiple sensor types. Pulse counting uses a 16-bit counter, while frequency measurement spans 0.5 Hz to 20 kHz. Front LEDs show F(ault), R(un), W(arning), P(rimary), and per-channel P(ulse) and F(ault) status, giving technicians a fast visual check during commissioning.

Technical Specs That Matter on the Floor
The signal specification is 24 V d.c. (19.2 – 32 V d.c.), matching common industrial transducer supplies. Groupwise isolation from ground and a rated insulation voltage of 50 V support safe separation in mixed-signal cabinets. Built-in current-limited sensor power simplifies wiring for NAMUR and 12 V or 24 V sensors without external limiting resistors. Maximum field cable length reaches 200 meters (218 yards), which covers most plant-floor runs from remote transmitters. Power dissipation is 4 W, and current consumption on the +5 V Modulebus is 115 mA. The module carries CE marking and electrical safety approvals to EN 61010-1 and UL 61010-1, with hazardous-location ratings for C1 Div 2 cULus, C1 Zone 2 cULus, and ATEX Zone 2. Operating temperature is 0 to +55 °C (+32 to +131 °F), with approvals issued for +5 to +55 °C. Protection class is IP20 according to IEC 60529, and corrosion protection meets ISA-S71.04: G3.
Surplus Advantage and Sourcing Guidance
Autronexa supplies genuine surplus and refurbished ABB S800 modules like this one, each tested against OEM datasheet specifications and functionally verified by our sourcing team. For a module with eight channels and advanced diagnostics, that verification matters: a single failed channel can distort pulse totals or speed readings. Refurbished units are checked for channel function, LED indication, and communication integrity before shipping. When specifying a replacement, confirm the exact article number 3BSE028926R1 and the keying code CF. This unit works with Module Termination Units TU810, TU812, TU814, TU818, TU830, TU833, TU842, TU843, TU844, TU845, TU852, and TU854; verify your existing MTU before ordering. Also confirm whether your application requires single or redundant configuration, since the module supports both. Please verify current lifecycle status and availability with Autronexa before ordering. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this a genuine ABB DP840 module, or a clone?
Autronexa verifies every unit against OEM datasheet markings and part-number cross-reference. The DP840 is supplied as genuine surplus or professionally refurbished stock, not a grey-market copy.
What condition will the DP840 arrive in?
Our default condition is refurbished: each module is tested against OEM datasheet specifications and functionally verified by our sourcing team before shipment.
How fast can you ship the DP840?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability; surplus and refurbished units are ready to ship when in stock.
Which Module Termination Units work with the DP840?
The module is compatible with TU810, TU812, TU814, TU818, TU830, TU833, TU842, TU843, TU844, TU845, TU852, and TU854. Confirm your existing MTU and keying code CF before ordering.
Does the DP840 support redundant applications?
Yes. The module can be used in both single and redundant applications, and its advanced diagnostics support either configuration.
Related & compatible parts
ABB
AI820
Genuine surplus ABB AI820 analog input module — 4 bipolar differential channels, 14-bit resolution, verified and ready to…
ABB
CI540
Genuine surplus ABB CI540 S100 I/O Bus Extension module — verified condition, tested against OEM datasheet specs, ready…
ABB
CI920AN
Genuine surplus ABB CI920AN communication interface for S900 I/O — PROFIBUS DP-V1, verified condition, ready to ship.
ABB
CI845
Genuine surplus ABB CI845 Ethernet FCI module for Select I/O and S800 — verified, tested, and ready to…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…