ABB Cables & Connectors

ABB TB820V2

Cluster Modem I/O Module 3BSE013208R1

Manufacturer: ABB Part Number: TB820V2

Genuine surplus ABB TB820V2 Cluster Modem — fiber optic ModuleBus interface, verified condition, faster lead time than OEM.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Article Number 3BSE013208R1
Communication Protocol Modulebus
Master or Slave Slave
24 V Consumption typ. 100 mA
Operating Temperature 0 to +55 °C (+32 to +131 °F), approvals for +5 to +55 °C
Storage Temperature -40 to +70 °C (-40 to +158 °F)
Protection Class IP20 according to EN60529, IEC 529
Corrosion Protection ISA-S71.04: G3
Dimensions (W×H×D) 58 mm × 170 mm × 122 mm
Weight 0.3 kg (0.66 lbs)

Description

When a fiber optic ModuleBus link fails, every I/O cluster behind it goes dark. The ABB TB820V2 Cluster Modem I/O Module 3BSE013208R1 restores that link — a genuine surplus unit verified by Autronexa, ready to ship at a fraction of OEM list price.

What This Module Does in an S800 I/O Station

The TB820V2 is the fiber optic interface to the ModuleBus in ABB’s S800 I/O system. It bridges the electrical ModuleBus — which supports up to 12 I/O modules — to the optical ModuleBus, where up to seven clusters can connect. That architecture matters for cost: instead of running long electrical backplanes or adding controllers, you distribute I/O clusters locally over fiber and keep copper runs short. A rotary switch selects cluster number 1 to 7 on the optical bus, so one spare unit covers any cluster position in your station. The module also handles supervisory functions for the I/O ModuleBus and power supply, and provides an isolated power supply to the I/O modules — protection that prevents a fault in one cluster from cascading into adjacent hardware.

Figure 1: Front view of the ABB TB820V2 Cluster Modem I/O Module 3BSE013208R1 showing its physical design and enclosure.

Technical Profile and Environmental Cost Implications

Power draw is typically 100 mA at 24 V, so the module adds negligible load to station supplies. The IP20 rating and 0 to +55 °C operating range suit cabinet-mounted installations; note that approvals are issued for +5 to +55 °C, and vertical mounting limits ambient to 40 °C — plan panel layout accordingly to avoid derating surprises. Corrosion protection meets ISA-S71.04: G3, which matters in pulp, paper, and chemical plants where airborne contaminants shorten electronics life. The unit carries CE marking, EN 61010 and UL 61010 electrical safety approvals, ATEX Zone 2 and cULus Class I Div 2 hazardous-location ratings, plus marine certificates from ABS, BV, DNV-GL, and LR — certifications that would cost significant time and money to re-qualify on a replacement design. Dimensions are 58 mm wide, 170 mm high including latch, 122 mm deep, at 0.3 kg.

Figure 2: Technical layout and connection details for the ABB TB820V2 Cluster Modem I/O Module 3BSE013208R1.

Why Genuine Surplus Beats Waiting on OEM Lead Time

ABB’s S800 I/O family is widely deployed, but new-from-OEM lead times on individual modules can stretch weeks — and a stopped process line costs far more than the part. Autronexa stocks genuine surplus and refurbished unit units tested against OEM datasheet specifications and functionally verified by our sourcing team. You get the exact article number 3BSE013208R1, not a cross-referenced substitute, with clear condition notes and current availability before you commit. For maintenance teams holding spares budgets, refurbished units typically deliver meaningful savings versus OEM list price while keeping the certification pedigree intact. Contact Autronexa with your part number for verified condition and current availability.

Frequently asked questions

Is this TB820V2 a genuine ABB module or a clone?

Every unit is verified against OEM datasheet markings and part-number cross-reference before listing. Autronexa supplies genuine surplus and refurbished ABB components only.

What condition will the TB820V2 arrive in?

Our default condition is Refurbished — tested against OEM datasheet specifications and functionally verified by our sourcing team. Condition notes are provided before purchase.

How fast can Autronexa ship the TB820V2?

Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability; surplus units typically ship faster than OEM factory orders.

Does the TB820V2 work with my existing S800 I/O cluster?

The module connects the electrical ModuleBus (up to 12 I/O modules) to the optical ModuleBus (up to seven clusters). The rotary switch selects cluster number 1 to 7, so it fits any cluster position in an S800 station.

Is the TB820V2 still supported by ABB?

Lifecycle status varies by region and date. Contact Autronexa to verify current OEM support status and availability before ordering.

Related & compatible parts

ABB

07 KT 94

Genuine surplus ABB 07 KT 94 Advant Controller with 24 DI, 16 DO, 8 AI/O, 4 AO —…

In Stock

ABB

AI563

Genuine surplus ABB AI563 analog input module with 4 configurable thermocouple inputs. Verified condition and fast lead times…

In Stock

ABB

AX522

Genuine surplus ABB AX522 analog I/O module — 8 AI, 8 AO, 12-bit, verified and ready to ship…

In Stock

ABB

V18345-2010420001

Genuine surplus ABB TZIDC positioner, 4–20 mA two-wire, IP 65, double acting fail safe — verified condition and…

In Stock

News & guides for ABB

View all articles

Request a quote for this part

Part number: TB820V2

We reply within one business day.