ABB TU805
Kit consisting
Genuine surplus ABB TU805 kit — 10 terminal units for DI801/DO801, 16 channels, 50 V, verified condition and ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Article Number | 3BSE035990R1 |
|---|---|
| Channels | 16 |
| Voltage | 50 V |
| Use With I/O | DI801, DO801 |
| Maximum Current per I/O Channel | 1 A |
| Acceptable Wire Sizes | Solid: 0.2 - 1.5 mm²; Stranded: 0.2 - 1.5 mm², 24- 16 AWG |
| Operating Temperature | 0 to +55 °C (+32 to +131 °F); approvals issued for +5 to +55 °C |
| Protection Class | IP20 according to IEC 60529 |
| Corrosion Protection | ISA-S71.04: G3 |
| Weight | 0.3 kg |
Description
When an S800 I/O module needs its field wiring landed, the terminal unit is what turns a bare module into a working channel bank. The ABB TU805 kit (10 pieces) gives you 16-channel, 50 V passive terminal units for DI801 and DO801 modules — and sourcing it as genuine surplus means you get verified units without waiting on OEM allocation. Autronexa supplies tested, refurbished kits with clear lead times.
What the TU805 Terminal Unit Does in an S800 I/O System
The terminal unit is the passive interface between the process wiring and the I/O module. It distributes external process power and provides the screw terminals for field connections. Each unit handles 16 channels and supports 2- and 3-wire connections of process signals. It mounts directly on the I/O module, so it adds no extra panel space — a practical detail when you are retrofitting an existing cabinet.
The kit contains 10 terminal units, which matches the way most maintenance teams buy: enough to cover a full rack of DI801 or DO801 modules in one order. Process power distribution is handled through 2 x 2 process power terminals and 2 x 16 process power distribution terminals. Maximum current per I/O channel is 1 A.

Wiring, Environmental, and Certification Details That Matter on Site
Acceptable wire sizes are solid 0.2 – 1.5 mm² and stranded 0.2 – 1.5 mm², 24- 16 AWG. That range covers the typical field cabling used on 50 V digital signals, so you can land existing wiring without adapters.
The unit carries CE marking and is built to EN 61010-1 and UL 61010-1 electrical safety standards. For hazardous areas, it holds C1 Div 2 cULus, C1 Zone 2 cULus, and ATEX Zone 2 approvals, plus DNV-GL marine certification. Operating temperature is 0 to +55 °C, with approvals issued for +5 to +55 °C. Corrosion protection is rated ISA-S71.04: G3, and the IP20 protection class suits cabinet-mounted use. Pollution degree is 2 per IEC 60664-1. These ratings matter when the panel sits in a process environment rather than a clean control room.

Why Genuine Surplus Fits This Terminal Unit
Terminal units are passive, so they age slowly — there are no firmware revisions or calibration routines to worry about. That makes professionally refurbished units a practical alternative to new OEM stock. Autronexa verifies each kit against OEM datasheet markings and part-number cross-reference, and units are tested against OEM datasheet specifications and functionally verified by our sourcing team.
The kit format is also an advantage: buying 10 units at once covers spare capacity for future module additions. If you are maintaining an installed S800 I/O base, this is the kind of part where surplus stock keeps a project moving while an OEM order is quoted. Please verify current lifecycle status and availability with Autronexa before ordering.
Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this ABB TU805 kit genuine, or a third-party copy?
Autronexa verifies every kit against OEM datasheet markings and part-number cross-reference. The article number 3BSE035990R1 and the 10-piece kit configuration are checked before the unit is listed. We do not supply clones or grey-market copies.
What condition will the TU805 kit arrive in?
Our default condition is refurbished: units are tested against OEM datasheet specifications and functionally verified by our sourcing team. If you need a specific condition grade, contact Autronexa before ordering and we will confirm what is available.
How fast can Autronexa ship the TU805 kit?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability — we will confirm the ship date before you commit to the order.
Does the TU805 work with both DI801 and DO801 modules?
Yes. The terminal unit is specified for use with S800 I/O modules DI801 and DO801. It provides 16 channels and supports 2- and 3-wire connections of process signals, with a maximum current of 1 A per I/O channel.
Is the TU805 still supported by ABB?
Lifecycle status is not stated in the datasheet we hold. Contact Autronexa to verify OEM support status and current availability before you plan a long-term spares strategy around this part.
Related & compatible parts
ABB
ACS880-01-156A-5
Genuine surplus ABB ACS880-01-156A-5 wall-mounted drive, 90 kW, 156 A — verified condition, tested, and ready to ship…
ABB
FENA-21
Genuine ABB FENA-21 dual-port Ethernet adapter for drives — PROFINET IO, EtherNet/IP, Modbus TCP. Verified surplus, ready to…
ABB
AI531
Genuine surplus ABB AI531 analog input module — 8 channels for U, I, RTD, R, TC and DI,…
ABB
DI810
Genuine surplus ABB DI810 digital input module, 16 channels, 24 V d.c., S800 mechanics — verified condition from…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…