ABB TU848
Module Termination Unit
Genuine surplus ABB TU848 termination unit for redundant TB840/TB840A modem setups — verified condition, ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Article Number | 3BSE042558R1 |
|---|---|
| Power Input | 24 V d.c (19.2–30 V) |
| ModuleBus Current Distribution | Maximum 5 V 1.5 A; 24 V 1.5 A |
| Power Dissipation | 2.5 W |
| Acceptable Wire Sizes | Solid: 0.2–2.5 mm²; Stranded: 0.2–2.5 mm², 24–12 AWG |
| Recommended Torque | 0.5 Nm |
| Operating Temperature | 0 to +55 °C (approvals issued for +5 to +55 °C) |
| Ingress Protection | IP20 according to IEC 60529 |
| Dimensions (W × H × D) | 124 mm × 186.5 mm × 47 mm; 0.45 kg |
Description
When a redundant ModuleBus segment drops, every hour of downtime pressures maintenance and procurement alike. The ABB TU848 Module Termination Unit (article 3BSE042558R1) is the passive interface that ties two TB840/TB840A optical modems to redundant I/O with dual 24 V d.c power feeds — and genuine surplus stock shortens the wait versus OEM lead time.
What This Termination Unit Does in a Redundant I/O System
The TU848 sits between the optical modems and the I/O rack. It carries connections for a double power supply (one feed per modem), a double electrical ModuleBus, and two TB840/TB840A modems, so a single failed modem or feed does not take the segment down. A rotary switch sets the cluster address from 1 to 7, and two mechanical keys — six positions each, 36 combinations — block insertion of the wrong module type. The unit is passive and DIN rail mounted, with a latching device for locking and grounding. Note that termination unit TU849 serves non-redundant I/O; this unit is the redundant variant.

Electrical and Mechanical Details Buyers Should Confirm
Power input is 24 V d.c (19.2–30 V), with ModuleBus current distribution of maximum 5 V 1.5 A and 24 V 1.5 A; power dissipation is 2.5 W. Wiring accepts solid 0.2–2.5 mm² and stranded 0.2–2.5 mm² (24–12 AWG) at a recommended torque of 0.5 Nm. The housing measures 124 mm wide, 186.5 mm high including latch, and 47 mm deep, at 0.45 kg. Operating temperature is 0 to +55 °C, with approvals issued for +5 to +55 °C; vertical mounting caps ambient at 40 °C. Ingress protection is IP20, and the unit carries CE marking plus EN 61010-1 and UL 61010-1 electrical safety listings.
Why Genuine Surplus Fits This Model
Redundant ModuleBus architectures are usually kept running well past their OEM sales window, so replacement termination units get scarce exactly when a shutdown is scheduled. Autronexa stocks surplus and refurbished units tested against OEM datasheet specifications and functionally verified by our sourcing team. Compared with brand-new distributor channels, surplus shortens the wait; compared with grey-market sellers, every unit is checked against OEM markings and the 3BSE042558R1 article number. Confirm your revision and cluster-address plan before ordering. Please verify current lifecycle status and availability with Autronexa before ordering.
Frequently asked questions
Is this a genuine ABB TU848, or a clone?
Autronexa verifies each unit against OEM datasheet markings and cross-references the article number 3BSE042558R1 before it enters stock. We do not sell unverified copies.
What condition will the TU848 arrive in?
Units ship in the site default condition, Refurbished — tested against OEM datasheet specifications and functionally verified by our sourcing team. Ask us for the condition note on the specific unit reserved for you.
How fast can you ship a TU848?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability before committing to a maintenance window.
Does the TU848 work with both TB840 and TB840A modems?
Yes — the datasheet lists it for redundant configuration of TB840/TB840A optical modems, with two modem connections and dual 24 V d.c power feeds.
Is the TU848 still supported by ABB?
Lifecycle status is not stated in our source data. Contact Autronexa to verify OEM support status and availability for your installed base.
Related & compatible parts
ABB
TU846
Genuine surplus ABB TU846 termination unit for redundant CI840/CI840A and I/O — verified condition, practical lead times.
ABB
V18347-2041150001
Genuine surplus ABB TZIDC-120 electro-pneumatic positioner with FOUNDATION Fieldbus, ATEX EEx ia IIC T6, verified and ready to…
ABB
AI930B
Genuine surplus ABB AI930B analog input module — 4 channels, 4...20 mA, HART, ATEX Zone 2. Verified condition,…
ABB
TK812V150
Genuine surplus ABB TK812V150 POF cable, 15 m simplex, for Optical ModuleBus. Verified condition and fast sourcing from…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…