Bently Nevada Vibration Monitoring 3500

Bently Nevada 3500/61-01-00

Temperature Monitors with Recorder Outputs

Manufacturer: Bently Nevada Part Number: 3500/61-01-00

Bently Nevada 3500/61-01-00 Temperature Monitors with Recorder Outputs. RTDs: 100Ω 3-wire & 4-wire platinum.

  • Available on request
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

Technical specifications

Manufacturer Bently Nevada
Product No. 3500/61-01-00
Product type Temperature Monitors with Recorder Outputs
I/O Module Type 01 = RTD/TC Non-isolated I/O Module Internal Terminations
Agency Approval Option 00 = None
Signal Accepts from 1 to 6 RTD or TC transducer signals.
Impedance 10 MΩ for each lead input.
Power Consumption 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts.
TCs Type E -100 °C to +1000 °C, (-148 °F to +1832 °F).
When using any of the isolated thermocouple I/O modules (-03 or -04
RTDs 100Ω 3-wire & 4-wire platinum
RTD (alpha = 0.00385) -200° C to +850° C (-328 °F to +1562 °F). With external barriers: -50 °C to +850 °C (-122 °F to +1562 °F). 100Ω 3-wire & 4-wire platinum
Platinum RTD's with 0.00385 alphas are the worldwide industrial standard and are recommended for all applications
System Isolation 500Vdc Channel to Channel Isolation: 250 Vdc
Isolation is only required for fault scenarios and these voltages will not be present on the I/O module inputs when a wiring or field fault occurs.
Temperature Monitor is operating properly.
Monitor is communicating with other modules in the 3500 rack.
RTD Current Source Value 925 ±15 µA @ 25° C per transducer (single supply for the 4-wire RTD and two supplies for the 3-wire).
Recorder +4 to +20 mA. Values are proportional to monitor full-scale. Individual recorder values are provided for each channel. Monitor operation is unaffected by short circuits on recorder outputs.
Voltage Compliance (current output) 0 to +12 Vdc range across load. Load resistance is 0 to 600 Ω.
Resolution 0.3662 µA per bit ±0.15% error at room temperature ±0.4% error over temperature range.
Signal Conditioning Specified at +25 °C (+77 °F) unless otherwise noted.
Full-scale range for each channel is set in the field via 3500 Configuration Software. No calibration is required. RTDs and TCs (except for 10Ω Copper RTDs) Resolution 1 °C or 1 °F
Rack ±3 °C at 25 °C (±5.4 °F at 77 °F).
Rack ±1 °C at 25 °C (±1.8 °F at 77 °F).
Rack ±2 °C at 25 °C (±3.6 °F at 77 °F). ±3 °C at 25 °C ±5.4 °F at 77 °F).
Rack ±3 °C at 25 °C ±5.4 °F at 77 °F).
Rack °C at 25 °C (±1.8 °F at 77 °F) 10 Ω Copper RTDs Resolution 1°C or 1 °F Accuracy ±3 °C at 25 °C
Monitors have both under and over alarm setpoints.
The user can program alarm delays using software as follows:
Alert From 1 to 60 seconds in 1 second intervals.
Danger From 1 to 60 seconds in 0.5 second intervals
Temprature -30°C to +65°C (-22°F to +150 °F) when used with
I/O Modules 0°C to +65 °C (32 °F to +150 °F) when used with Internal Barrier
Temperature -40°C to +85°C (-40°F to +185°F)
Dimensions (Height x Width x
Depth) 241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in)
Depth) 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
Depth) 241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42 in)
Module 1 full-height front slot

Description

The Bently Nevada 3500/61-01-00 is a temperature monitors with recorder outputs for the 3500 Machinery Protection System. It conditions field transducer signals into vibration and position measurements and compares them against programmable alarm setpoints inside the 3500 rack. and has a nominal power consumption of 3500/60 nominal consumption of 7 watts. 3500/61 nominal consumption of 9 watts. with 500vdc channel to channel isolation: 250 vdc Dimensions are (height x width x It monitors critical rotating equipment such as turbines, compressors, and pumps, and communicates monitor status and measured values to the 3500 rack and to recorder outputs for machinery protection. Configuration is performed with 3500 Rack Configuration Software; no field calibration is required.

Product Identification

  • Manufacturer: Bently Nevada.
  • Product No.: 3500/61-01-00.
  • Product type: Temperature Monitors with Recorder Outputs.

Ordering & Configuration

  • I/O Module Type: 01 = RTD/TC Non-isolated I/O Module Internal Terminations.
  • Agency Approval Option: 00 = None.
  • Signal Accepts from 1 to 6 RTD or TC: transducer signals..

Electrical & Signal

  • Impedance: 10 MΩ for each lead input..
  • Power Consumption: 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts..
  • System Isolation: 500Vdc Channel to Channel Isolation: 250 Vdc.
  • RTD Current Source Value: 925 ±15 µA @ 25° C per transducer (single supply for the 4-wire RTD and two supplies for the 3-wire)..
  • Recorder: +4 to +20 mA. Values are proportional to monitor full-scale. Individual recorder values are provided for each channel. Monitor operation is unaffected by short circuits on recorder outputs..
  • Voltage Compliance (current output): 0 to +12 Vdc range across load. Load resistance is 0 to 600 Ω..
  • Resolution: 0.3662 µA per bit ±0.15% error at room temperature ±0.4% error over temperature range..
  • Signal Conditioning: Specified at +25 °C (+77 °F) unless otherwise noted..
  • Full-scale range for each: channel is set in the field via 3500 Configuration Software. No calibration is required. RTDs and TCs (except for 10Ω Copper RTDs) Resolution 1 °C or 1 °F.
  • The user can program alarm delays using: software as follows:.

Environmental Ratings

  • Temperature Monitor is: operating properly..
  • Temperature: -40°C to +85°C (-40°F to +185°F).

Physical & Mechanical

  • Dimensions: (Height x Width x.

Specifications

  • TCs: Type E -100 °C to +1000 °C, (-148 °F to +1832 °F)..
  • When using any of the isolated: thermocouple I/O modules (-03 or -04.
  • RTDs: 100Ω 3-wire & 4-wire platinum.
  • RTD (alpha: = 0.00385) -200° C to +850° C (-328 °F to +1562 °F). With external barriers: -50 °C to +850 °C (-122 °F to +1562 °F). 100Ω 3-wire & 4-wire platinum.
  • Platinum RTD's with: 0.00385 alphas are the worldwide industrial standard and are recommended for all applications.
  • Isolation is only required for: fault scenarios and these voltages will not be present on the I/O module inputs when a wiring or field fault occurs..
  • Monitor is communicating with: other modules in the 3500 rack..
  • Rack: ±3 °C at 25 °C (±5.4 °F at 77 °F)..
  • Rack: ±1 °C at 25 °C (±1.8 °F at 77 °F)..
  • Rack: ±2 °C at 25 °C (±3.6 °F at 77 °F). ±3 °C at 25 °C ±5.4 °F at 77 °F)..
  • Rack: ±3 °C at 25 °C ±5.4 °F at 77 °F)..
  • Rack: °C at 25 °C (±1.8 °F at 77 °F) 10 Ω Copper RTDs Resolution 1°C or 1 °F Accuracy ±3 °C at 25 °C.
  • Monitors have both under and: over alarm setpoints..
  • Alert From 1 to 60 seconds in 1 second: intervals..
  • Danger From 1 to 60 seconds in 0.5: second intervals.
  • Temprature: -30°C to +65°C (-22°F to +150 °F) when used with.
  • I/O Modules: 0°C to +65 °C (32 °F to +150 °F) when used with Internal Barrier.
  • Depth): 241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in).
  • Depth): 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in).
  • Depth): 241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42 in).
  • Module: 1 full-height front slot.

Model Comparison

Compare the 3500/61-01-00 against the closest Bently Nevada configurations below to confirm ordering options, ratings and physical interchange.

Model Product No. I/O Module Type Agency Approval Option Power Consumption Manufacturer Product type Signal Accepts from 1 to 6 RTD or TC Impedance
3500/61-01-00 3500/61-01-00 01 = RTD/TC Non-isolated I/O Module Internal Terminations 00 = None 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.
3500/61-01-01 3500/61-01-01 01 = RTD/TC Non-isolated I/O Module Internal Terminations 0 1= CSA/NRTL/C (Class 1, Div 2) 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.
3500/61-01-02 3500/61-01-02 01 = RTD/TC Non-isolated I/O Module Internal Terminations 0 2 = ATEX/ IECEx/ CSA (Class 1, Zone 2) 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.
3500/61-02-00 3500/61-02-00 0 2 =RTD/TC Non-isolated I/O Module 00 = None 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.
3500/61-05-00 3500/61-05-00 0 5= RTD/TC Non-isolated I/O Module with Internal Barriers 0 0 =None 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.
3500/61-02-01 3500/61-02-01 0 2= RTD/TC Non-isolated I/O Module 0 1= CSA/NRTL/C (Class 1, Div 2) 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.
3500/61-02-02 3500/61-02-02 0 2 = RTD/TC Non-isolated I/O Module 0 2 = ATEX/ IECEx/ CSA (Class 1, Zone 2) 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts. Bently Nevada Temperature Monitors with Recorder Outputs transducer signals. 10 MΩ for each lead input.

Frequently asked questions

What is the Bently Nevada 3500/61-01-00 and what does it do?

The Bently Nevada 3500/61-01-00 is a temperature monitors with recorder outputs for the 3500 Machinery Protection System. It conditions field transducer signals into vibration and position measurements and compares them against user-programmable alarm setpoints within the 3500 rack.

What is the power consumption of the 3500/61-01-00?

The 3500/61-01-00 has a nominal power consumption of 3500/60 Nominal consumption of 7 watts. 3500/61 Nominal consumption of 9 watts. It draws power from the 3500 rack backplane and requires no separate supply.

What are the physical dimensions of the 3500/61-01-00?

The 3500/61-01-00 measures (Height x Width x and weighs It occupies a standard 3500 rack slot and installs on the rack backplane.

How is the 3500/61-01-00 installed and configured?

The 3500/61-01-00 mounts in a 3500 rack rear slot and draws power from the rack backplane. Channels are configured with 3500 Rack Configuration Software; alarm setpoints and full-scale ranges are set in software with no field calibration required.

Related & compatible parts

Bently Nevada · 3500

3500/94M-05-00-00

Bently Nevada 3500/94M-05-00-00 VGA Display Module. Display Size and Mounting: 15" display, 19" rack mount; Screen Size: 15”…

Available on request

Bently Nevada · 3500/40M

129525-0100-01

Bently Nevada 129525-0100-01 Transducer Cable. Cable Length: 100 feet (30.5 metres); Assembly: Not assembled.

Available on request

Bently Nevada

3500/60-01-01

Bently Nevada 3500/60-01-01 Temperature Monitor Module. Agency Approval: CSA/NRTL/C (Class 1, Div 2). New surplus stock, ships within…

Available on request

Bently Nevada · 3500/40M

132234-01

Bently Nevada 132234-01 External Termination Block. Connector Type: Terminal strip connectors. Supplied for MRO and OEM replacement use.

Available on request

News & guides for Bently Nevada

View all articles

Request a quote for this part

Part number: 3500/61-01-00

We reply within one business day.

3500/61-01-00 Quote reply within 1 business day