Bently Nevada 3500/06 Weatherproof Housing: Ratings, Purging and Mounting Limits

TL;DR: The weatherproof enclosure for a Bently Nevada 3500 rack is the 3500/06, not the 3500/01 — 3500/01 is the Rack Configuration Software. Datasheet 141528 Rev. H does not publish a NEMA 4X or IP66 rating for the 3500/06; it describes a purged weatherproof housing in epoxy-coated steel or 304 stainless steel. No heater, fan, vortex cooler, seismic rail or vibration-isolation mount appears in the ordering table. Rack temperature is set by the module ratings plus the datasheet derating curve, and the housing must not be installed in direct sunlight.
Spare-parts listings often merge several different Bently Nevada products into one description: a 3500 rack housing, a NEMA 4X/IP66 fiberglass enclosure, a heater kit and a seismic mounting rail. This guide separates them and checks each claim against the 3500/06 datasheet (141528 Rev. H), the 3500/05 rack specification (document 141525) and the 3500/60 and 3500/61 temperature module datasheet (141540 Rev. L).
What is the Bently Nevada 3500/06 weatherproof housing?
The 3500/06 is a bolt-on weatherproof enclosure for a 3500 full-size or mini-rack. It shields the rack from moisture, dirt, grime and unclean air, and accepts an optional air-purge system for hazardous-area installations. It is made of epoxy-coated steel or 304 stainless steel and weighs 22.7 kg before conduit or purge hardware.
The housing is ordered as 3500/06-AA-BB-CC-DD. It accepts a full-size or mini 3500 rack in the rack-mount format, and it accepts internal barrier I/O modules. The 3500/05 datasheet states that the 3500/06 is not compatible with the bulkhead mount option, so a bulkhead rack cannot be moved into this housing.
The front is a hinged door that latches at 90° and 135°, and the rear is a bolted cover. The datasheet does not list an observation window. All field wiring enters through conduits mounted to the housing, not through glands on the door. For the rack layout and slot allocation behind the door, see the Bently Nevada 3500 rack architecture guide.
Is the 3500/06 rated NEMA 4X or IP66?
The 3500/06 datasheet publishes neither NEMA 4X nor IP66. It calls the product a weatherproof housing and relies on door seals plus an optional air purge, not on a NEMA or IEC enclosure rating. NEMA 4X and IP66 are separate standards: NEMA 4X adds a corrosion-resistance requirement, while IP66 covers dust tightness and powerful water jets.
NEMA 4X is defined in NEMA 250. It requires a watertight and dust-tight enclosure and adds a corrosion-resistance requirement. IP66 is defined in IEC 60529: the first 6 means dust-tight, and the second 6 means protection against powerful water jets. A product can carry both ratings, but each one must be tested to its own standard. Neither rating appears anywhere in the 3500/06 datasheet.
The windowed fiberglass NEMA 4X/IP66 housing that appears in Bently Nevada catalogues is part number 105M6193-01. It is used with the 1900/65A general-purpose monitor and the 2300 series vibration monitors, not with a 3500 rack. The 2300-series stainless steel version is a separate item, such as the 105M6193-02 stainless steel housing. Quoting that part number for a 3500 weatherproof housing is a product-family error.
| Claim | Standard or source | What it covers | Status for the 3500/06 |
|---|---|---|---|
| NEMA 4X | NEMA 250 | Watertight, dust-tight, corrosion-resistant enclosure | Not published in 141528 Rev. H |
| IP66 | IEC 60529 | Dust-tight; protected against powerful water jets | Not published in 141528 Rev. H |
| Weatherproof plus air purge | Datasheet 141528 Rev. H | Door seals; optional NFPA 496 Type Y or CEC 10x purge | Published |
| Agency approval | Ordering option D; guide 108M1756 | Country- and system-specific approvals | Option D = 00 None in Rev. H |
Approvals need their own sentence. The 3500 system is offered as a SIL 2-rated system, and the Baker Hughes product page lists hazardous-area and country-specific approvals. The housing datasheet, Rev. H, instead shows a compliance heading marked “Approvals Pending”, lists RoHS Directive 2011/65/EU, and gives agency approval option 00 None. Treat system-level SIL and area approvals as separate from the housing’s own listing, and confirm the exact certificate in the Approvals Quick Reference Guide 108M1756.
What temperature can a 3500 rack hold inside the 3500/06?
The housing has no active temperature control. The 3500/60 and 3500/61 monitor datasheets rate -30 °C to +65 °C with internal or external termination I/O, and 0 °C to +65 °C with internal barrier I/O. The 3500/06 adds a temperature rise above ambient that depends on rack power dissipation, shown on the datasheet derating graph.
The rack modules set the limit, not the enclosure. The 3500/60 and 3500/61 datasheet (141540 Rev. L) gives -30 °C to +65 °C with internal or external termination I/O modules, and 0 °C to +65 °C with internal barrier I/O modules. Storage is -40 °C to +85 °C, and humidity is 95% non-condensing.
Inside the housing, the air temperature is the site ambient plus the rise caused by rack power dissipation. The 3500/06 datasheet provides a derating graph of temperature rise above ambient versus dissipated watts. Read the graph with the actual rack load, then compare the result with the lowest-rated module in the rack. The datasheet also warns that the housing should not be used in direct sunlight because the 3500 system dissipates heat; exceeding the monitor temperature can degrade reliability and potentially ignite some gases.
The temperature monitors themselves are ordered separately; the 3500/60 and 3500/61 temperature monitor page lists the RTD/TC and I/O options.
| Function | 3500/06 accessory | Status |
|---|---|---|
| Cold-start or freeze protection | None listed | Not published |
| Fan-assisted cooling | None listed | Not published |
| Vortex cooler | None listed | Not published |
| Air purge | Option C -01 or -02 | Published; for hazardous-area pressurization, not cooling |
| Solar gain control | “Do not use in direct sunlight” | Installation restriction, not a kit |
Does Bently Nevada publish a heater, fan or vortex cooler for the 3500/06?
No. The 3500/06 ordering table lists only housing material, conduit fittings and air purge; it has no heater, fan or vortex cooler option. The purge hardware exists to meet NFPA 496 Type Y or Canadian Electrical Code 10x requirements, and its flow rates are specified for enclosure pressurization, not for heat removal.
The ordering table has four fields: A housing or door material, B conduit fitting, C air purge, and D agency approval. There is no thermal field. Air purge option -01 adds four 1-1/4-inch NPT poured seal fittings and a 1/4-inch NPT air input. Option -02 adds a gauge assembly, a bulkhead connector and a connecting tube. The added weights are 454 g for conduit option -01, 1.81 kg for purge option -01 and 3.18 kg for purge option -02.
Purge flow is specified for enclosure pressurization. At 1.0 inch of water, the 5X NFPA 496 table gives 1.08 cu ft/min and 14 minutes to purge; the 10X Canadian Electrical Code table gives a comparable flow with a shorter time at higher pressure. Static purge pressure must exceed 50.8 mm (2.0 in) of water, measured on the gauge after purging with the valve closed. These figures describe how quickly the housing is cleared, not how much heat it removes.
If a project needs heating or active cooling, that is an engineered auxiliary system outside the 3500/06 bill of materials. The datasheet does not publish a maintained internal temperature, a heater wattage or a cooler capacity, so those values must be designed and verified for the site rather than inferred from the housing.
Is there a seismic or vibration-isolating rail mount for the 3500?
No isolation rail is published. The 3500/05 rack supports panel, 19-inch EIA rack and bulkhead mounting; the 3500/06 housing accepts the full-size or mini rack-mount versions and is not compatible with the bulkhead option. Neither datasheet publishes a vibration-isolation mount, transmissibility figure or seismic qualification for the housing.
The 3500/05 rack has three mounting formats: panel mount, 19-inch EIA rack mount and bulkhead mount. The 3500/06 accepts the full-size and mini rack-mount versions. The 3500/05 datasheet explicitly excludes the bulkhead option from the weatherproof housing. Neither document publishes a resilient mount, an isolation rail, a transmissibility curve or a seismic qualification for the housing.
The housing attaches through eight clearance holes of 0.281 inch (7.14 mm) for 0.250-inch bolts or mounting studs, with thread-seal washers under all internal bolt or nut heads. Twelve holes are used when the air purge gauge assembly is fitted. That is a rigid bolted connection. If a site requires vibration isolation or seismic qualification, it is a project-specific support design, not a Bently Nevada accessory, and it must be qualified without breaking the door seal or the purge path.
How many racks fit, and how do cables enter the 3500/06?
A full-size 3500/05 rack provides 14 module slots and a mini-rack provides 7; the power supplies and Rack Interface Module occupy the fixed left positions. Cable entry uses four 1-1/4-inch NPT weatherproof hubs with conduit option -01. Upper conduits carry transducer, signal and recorder wiring; lower conduits carry power and relay wiring.
Capacity comes from the rack, not the housing. A full-size 3500/05 rack is a 19-inch EIA rack with 14 module slots; a mini-rack is a 12-inch rack with 7 slots. Power supplies and the Rack Interface Module must be installed in the far left positions. A mini-rack installed in an EIA rack needs the 144863-01 adapter panel.
| Item | Full-size rack | Mini-rack |
|---|---|---|
| Module slots (3500/05) | 14 | 7 |
| Dimension reference, item 2 (Figure 2) | 595.1 mm (23.43 in) | 417.3 mm (16.43 in) |
| Panel cutout (Figure 3) | 534.7 × 419.7 mm (21.050 × 16.525 in) | 356.87 × 292.74 mm (14.050 × 11.525 in) |
| Mounting holes | 8 × 7.14 mm (0.281 in) clearance | 8 × 7.14 mm (0.281 in) clearance |
| Housing weight | 22.7 kg (50 lb) | 22.7 kg (50 lb) |
| Conduit entry | 4 × 1-1/4 in NPT (option B -01) | 4 × 1-1/4 in NPT (option B -01) |
| Door | Hinged front, 90°/135° latch; bolted rear cover | Same |
Cable entry is through conduit option -01, which provides four 1-1/4-inch NPT weatherproof hubs. The datasheet separates the routing: both upper conduits are for transducer power, signal input and recorder output; both lower conduits are for power input and relay wiring. Power and relay wiring should not share a conduit with transducer, signal and recorder wiring.
The front door is hinged and latches at 90° and 135°; it must be opened to a position where it can latch or unlatch. The rear cover is bolted. The datasheet does not list a window, a door-mounted display or a cable gland on the door. Rack power and communications modules are listed separately, including the 3500/15 power supply and the 3500/22M TDI module.
What installation checks does the datasheet call out?
Mount the housing on a flat panel using the eight 0.281-inch clearance holes and put the supplied thread-seal washers under every internal bolt or nut head. Route wiring through the specified conduits and keep power/relay wiring out of the transducer and signal conduits. For purged installations, prove a static purge pressure above 50.8 mm (2.0 in) of water.
The housing is mounted to a panel, not directly to a concrete foundation. The datasheet gives the panel cutout and the bolt-hole pattern but does not publish a foundation design, anchor type or civil load. Use the panel or structure specified by the rack installation, and keep the door swing clearance.
For grounding, the 3500/05 documentation covers rack earthing, including the 3500/04-01 Internal Barrier Earthing Module when internal barriers are installed. The 3500/06 datasheet does not add a separate housing grounding lug, a lightning arrestor or a surge-protection requirement. Those items are not published; if the site requires them, specify them as part of the electrical installation and do not infer them from the housing drawing.
| Requirement | Published in 3500/06 or 3500/05 | Gap to close in design |
|---|---|---|
| Panel fixing | 8 clearance holes, panel cutout, thread-seal washers | Foundation or steel support design |
| Grounding | Rack earthing; 3500/04-01 for internal barriers | No separate housing grounding point published |
| Lightning and surge | None | Not published |
| Vibration isolation | None | Not published |
| Purge pressure | Above 50.8 mm (2.0 in) of water at the gauge | Site air supply and pressure alarm |
| Cable segregation | Upper signal, lower power/relay | Conduit routing and schedules |
What is 3500/01, and why is it confused with the housing?
3500/01 is the Rack Configuration Software, ordered as 3500/01-01; it configures all 3500 modules and is not an enclosure. A 3500 mini-rack requires 3500/01 software version 2.70 or later. The weatherproof enclosure is 3500/06, ordered with its own four-part code for material, conduit, purge and approval options.
The 3500/01 part number belongs to the 3500 Rack Configuration Software, ordered as 3500/01-01. It is the Windows-based tool used to configure the rack and its modules. The 3500/05 datasheet adds a version condition: a 3500 mini-rack requires 3500/01 software version 2.70 or later. No enclosure is ordered as 3500/01.
| Code | Field | Options |
|---|---|---|
| 3500/06 | Base product | Weatherproof housing |
| A | Housing or door material | 01 epoxy steel housing (full); 02 stainless housing (full); 03 epoxy door (full); 04 stainless door (full); 05 epoxy door (mini); 06 stainless door (mini); 07 epoxy housing (mini); 08 stainless housing (mini) |
| B | Conduit fitting | 00 none; 01 four 1-1/4 in NPT weatherproof hubs |
| C | Air purge | 00 none; 01 purge fittings (requires B -01); 02 fittings and gauge (requires B -01) |
| D | Agency approval | 00 none |
Field A selects a housing or a door only, in epoxy-coated steel or 304 stainless steel, for a full-size or mini-rack. Field B adds conduit fittings. Field C adds air purge hardware. Field D is the agency approval option; Rev. H lists only 00 None.
Frequently asked questions
Can the 3500/06 be installed in direct sunlight?
No. Datasheet 141528 Rev. H states that the housing should not be used in direct sunlight because the 3500 system dissipates heat. Provide a shade structure or an enclosure shelter, and calculate the internal temperature from the derating graph before commissioning. A sunshade is not a published Bently Nevada accessory, so it is a site-design item.
Does the 3500/06 include a heater for cold climates?
No heater is listed in the 3500/06 ordering table. The lowest published operating limit comes from the modules: -30 °C with internal or external termination I/O, and 0 °C with internal barrier I/O. If a site needs cold-start heating or freeze protection, design it as a separate system and verify that it does not create a hot spot or interfere with the purge path.
Can a bulkhead-mount 3500 rack be installed in the 3500/06?
No. The 3500/05 rack datasheet states that the 3500/06 weatherproof housing is not compatible with the 3500/05 bulkhead mount option. Use a panel-mount or 19-inch EIA rack-mount rack instead. The mini-rack also has no bulkhead option.
Is the 3500/06 the same as the NEMA 4X/IP66 fiberglass housing?
No. The fiberglass NEMA 4X/IP66 windowed housing is 105M6193-01, used with the 1900/65A monitor and 2300 series vibration monitors. The 3500/06 is a steel or stainless steel weatherproof housing for a 3500 rack, and its datasheet publishes no NEMA or IP rating. The two products protect different hardware and should not be quoted interchangeably.
Do I need to reconfigure the rack when it is moved into a 3500/06?
The housing does not change module addresses or setpoints, but re-verify the rack configuration after the move. Re-check three physical items: conduit segregation, purge pressure if the purge option is used, and internal temperature at the actual rack load. A mini-rack also needs 3500/01 software v2.70 or later.
Can I add vibration isolators between the rack and the housing?
There is no published isolator, torque value or transmissibility rating. The housing uses a rigid eight-bolt panel connection. Any resilient mount is a project-specific modification and must be qualified against the site’s vibration or seismic criteria, and it must not compromise the door seal, the purge pressure or the rack’s electrical bonding.
What cable entry and conduit separation does the housing require?
Conduit option B -01 provides four 1-1/4-inch NPT weatherproof hubs. Route transducer power, signal input and recorder output through the upper conduits, and power input and relay wiring through the lower conduits. Do not mix power and relay wiring with transducer, signal or recorder wiring in the same conduit.
Which approvals apply to the 3500/06 itself?
Rev. H lists RoHS Directive 2011/65/EU and agency approval option 00 None, under a heading that says approvals are pending. System-level SIL 2 and hazardous-area approvals are separate and country-specific. Confirm the exact certificate for the housing and the rack in the Approvals Quick Reference Guide 108M1756 before quoting a project.
Where these figures come from
Housing dimensions, weights, ordering codes, purge tables and installation notes: Bently Nevada 3500/06 Weatherproof Housing datasheet 141528 Rev. H. Rack slots, mounting formats, bulkhead incompatibility and the 3500/01 v2.70 condition: 3500/05 System Rack specifications and ordering information, document 141525. Module temperature limits: 3500/60 and 3500/61 Temperature Modules datasheet 141540 Rev. L. System-level SIL and approval statements: the Baker Hughes 3500 Machinery Protection Systems product page. The housing datasheet is available as PDF 141528.
Where the datasheet is silent — NEMA 4X, IP66, heater, fan, vortex cooler, seismic isolation, foundation, lightning protection and a housing grounding point — this article says “not published” rather than filling the gap with a supplier claim.
Related reading
- 3500/91 EGD gateway: Mark VIe interface and slot limits
- 3500/50M tachometer module: channels and alarms
- 32000 metric probe housing: construction and protection ratings
Last checked 12 November 2026 against datasheet 141528 Rev. H. Confirm the current revision with Baker Hughes before ordering.