ABB DI828
Cable length 200 meters
Genuine surplus ABB DI828 digital input module — 16 isolated channels, 120V AC/DC, verified and ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Article number | 3BSE069054R1 |
|---|---|
| Number of channels | 16 |
| Signal specification | 120 V a.c. / d.c. |
| Input voltage range, "1" | 77..130 V a.c., 75..130 V d.c. |
| Input impedance | 14.2 kΩ (a.c.) / 50 kΩ (d.c.) |
| Isolation | Individually isolated channels |
| Filter times (selectable) | 2,5 ±0.5, 5 ±1, 10 ±2, 20 ±4 ms |
| Power dissipation | Typ. 3.5 W |
| Operating temperature | 0 to +55 °C |
| Protection class | IP20 according to IEC 60529 |
Description
The ABB DI828 is a 16-channel 120 V a.c./d.c. digital input module for the S800 I/O system, built for maintenance and procurement teams who need reliable signal acquisition without paying OEM list prices or waiting weeks for new stock. Autronexa supplies this module as genuine surplus or professionally refurbished stock, each unit verified against OEM datasheet markings and functionally tested before dispatch.
What the DI828 Does in an S800 I/O Rack
This unit sits in an S800 I/O rack and accepts 16 digital inputs at 120 V a.c. or d.c., with each channel individually isolated. That isolation matters for cost: a fault on one field circuit stays on that channel instead of taking out a whole group, so you replace a single module rather than a rack section. The module uses current-sinking inputs and provides front-panel LEDs for fault, run, warning, and each channel’s 0/1 state — practical diagnostics that cut troubleshooting time on a live panel. Channel 1 can supervise voltage for channels 2–8, and channel 16 for channels 9–15; if the supervised voltage disappears, the module sets a channel error and turns on the warning LED, with the error readable from the ModuleBus. That built-in supervision reduces the need for separate voltage-monitoring relays, which trims both panel cost and wiring labour.

Technical Specs That Affect Your Cost and Uptime
The input voltage range is 77–130 V a.c. and 75–130 V d.c., so the module tolerates the brownouts and supply sag common on older plant circuits without nuisance trips. Input impedance is 14.2 kΩ (a.c.) / 50 kΩ (d.c.), and the module offers selectable filter times of 2.5 ±0.5, 5 ±1, 10 ±2, and 20 ±4 ms — you can tune response to reject contact bounce rather than replacing the module when a noisy field device causes false counts. Power dissipation is typically 3.5 W, and current consumption from the +5 V ModuleBus is typically 45 mA (max 60 mA), keeping rack power budget predictable. The module pairs with TU851 keying code MTUs and is rated IP20, 0 to +55 °C operating, with CE marking and marine certifications ABS, BV, DNV, and LR. Maximum field cable length is 200 meters for a.c. and 600 meters for d.c. — the d.c. allowance alone can save a repeater or a remote I/O drop on long runs.

Surplus and Refurbished: Why It Fits This Module
This unit is a mature S800 I/O part, and new-from-OEM lead times on mature automation hardware can stretch well beyond a planned outage window. Autronexa’s surplus and refurbished route gives you a verified alternative: every unit is checked against OEM datasheet specifications and functionally verified by our sourcing team, so you know the channel count, isolation, and supervision features are intact before it reaches your panel. Because these are genuine parts, verified, you avoid the risk of grey-market clones that may not meet the 2000 V a.c. dielectric test voltage or the EN 61010 safety standards the original carries. For maintenance managers, the practical gain is shorter downtime and a lower cost per spare than OEM list — and you can hold a verified spare on the shelf instead of gambling on a single source. Please verify current lifecycle status and availability with Autronexa before ordering.
Sourcing Checklist Before You Buy
Confirm the exact article number 3BSE069054R1 and that your rack uses the S800 mechanics with TU851 keying code MTUs — mismatched MTUs are the most common reason a replacement module will not seat. Decide whether you need surplus or refurbished condition and ask for the condition grade in writing. Check that your field wiring matches the current-sinking input type and that your supervision scheme uses channel 1 or 16 as intended. Autronexa can cross-reference your existing module and confirm compatibility before shipment; contact us with your part number for verified condition and current availability.
Frequently asked questions
Is this a genuine ABB DI828, or a clone?
Autronexa verifies every DI828 against OEM datasheet markings and part-number cross-reference (article number 3BSE069054R1) before it enters stock. We do not supply grey-market copies.
What condition will the DI828 arrive in?
Units ship in the condition stated on your quote — typically refurbished, tested against OEM datasheet specifications and functionally verified by our sourcing team. Ask for the condition grade in writing.
How fast can you ship the DI828?
Lead time depends on current stock. Contact Autronexa with your required quantity and we will confirm current availability and dispatch timing.
Does the DI828 work with my existing S800 rack?
The module uses S800 mechanics and TU851 keying code MTUs. Confirm your rack and MTU match before ordering; Autronexa can cross-reference your existing module.
Is the DI828 still supported by ABB?
Lifecycle status is not stated in our data. Contact Autronexa to verify OEM support status and current availability before you commit.
Related & compatible parts
ABB
FENA-21
Genuine ABB FENA-21 dual-port Ethernet adapter for drives — PROFINET IO, EtherNet/IP, Modbus TCP. Verified surplus, ready to…
ABB
AI810
Genuine surplus ABB AI810 analog input module — 8 channels, 12-bit, verified condition, ready to ship from Autronexa.
ABB
DO571
Genuine surplus ABB DO571 S500-eCo digital output module — 8 relay outputs, verified condition, faster lead time than…
ABB
AI931B
ABB AI931B I/O & Function Modules. Signal type: 4...20 mA; Mechanics: S900. Number of channels is 4. New…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…