General Electric IS215VPROH2BD
Structured around triple redundant VPRO boards
Genuine surplus General Electric IS215VPROH2BD turbine protection board for Mark VI systems, verified and ready to ship from Autronexa.
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
Description
The General Electric IS215VPROH2BD is a Mark VI turbine protection board that handles emergency overspeed protection with a 2 Hz to 20 kHz MPU pulse rate range. Maintenance teams choose genuine surplus or refurbished units to keep critical protection loops available without long OEM waits.
What this unit Does in a Mark VI System
This board sits in the protection module and executes the emergency trip function. It connects up to three trip solenoids through the TREG and TRPG terminal boards, and either terminal board can initiate a trip for fail-safe operation. The board also manages emergency stop functions and controls the twelve relays on the TREG, with nine relays arranged in three voting groups that influence solenoid activation. An Ethernet connection supports IONet communications with the control modules. Because this unit is obsolete per GE, sourcing a verified surplus unit is often the practical route to keep an existing protection module serviceable. Autronexa supplies genuine surplus and refurbished automation components with verified condition and clear lead times.

Key Specifications for Maintenance Planning
The MPU pulse rate range of 2 Hz to 20 kHz covers the speed signals this board expects, and the 0.05 percent of reading accuracy supports reliable overspeed detection. The board uses surface-mount technology and operates from a 24 V dc or 48 V dc voltage rating. Front-panel connectors J3, J4, J5, and J6 link to the TPRO and TREG terminal boards, while J7 accepts the 125 V DC power input. Eleven LEDs on the faceplate show run, status, and fail states, and a reset button is available on the front of the board. During installation, power down the VME I/O processor rack, seat the board with both hands on the levers, and tighten the captive screws before powering up and checking diagnostics.

Sourcing and Service Considerations
For maintenance engineers, the priority is a board that matches the Mark VI protection architecture and arrives in verified condition. Autronexa helps confirm the exact model and revision before shipment, so the replacement fits the existing rack and terminal board wiring. Surplus and refurbished units are inspected and functionally verified by the sourcing team, which shortens the path from failure to restored protection. Share your part number with Autronexa and we will confirm verified condition and current availability.
Frequently asked questions
Is the IS215VPROH2BD a genuine General Electric board?
Autronexa verifies each IS215VPROH2BD against OEM datasheet markings and part-number cross-reference before it is offered as genuine surplus or refurbished stock.
What condition will the IS215VPROH2BD arrive in?
The IS215VPROH2BD is supplied as refurbished stock, tested against OEM datasheet specifications and functionally verified by the Autronexa sourcing team.
How fast can Autronexa ship the IS215VPROH2BD?
The IS215VPROH2BD is listed as in stock. Contact Autronexa for current lead time and verified condition before placing your order.
Does the IS215VPROH2BD work with Mark VI protection modules?
The IS215VPROH2BD is part of the GE Mark VI series and connects to TPRO and TREG terminal boards through front-panel connectors J3, J4, J5, and J6.
Related & compatible parts
Honeywell
MLE-TN32A
Genuine surplus Honeywell MLE-TN32A digital output module with 32 open collector channels, verified condition and practical sourcing support…
Mitsubishi
MR-J3ENSCBL5M-L
Genuine Mitsubishi MR-J3ENSCBL5M-L encoder cable, 5 m, IP67, shielded, compatible with HC-RP, HF-SN/SP/JP, HG-SN/SR and HK-KT/RT/ST servo systems.
Bently Nevada · 31000 / 32000 Series
31000-16-05-00-068-03-02
Bently Nevada 31000-16-05-00-068-03-02 Proximity Probe Housing. Standoff Adapter: No standoff adapter; Probe Cable Length: 0.5 m (20 in).
Keyence
GL-R08L
Genuine surplus Keyence GL-R08L Type 4 light curtain set — 8 beams, 280 mm detection height, verified condition…
News & guides for General Electric
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…
Motion Control Precision: Servo Loops, Fieldbus Jitter, AI
Motion control precision depends on servo loop rates, fieldbus cycle times and jitter, sensor latency and mechanics. AI sits above…
Bently Nevada 3500/06 Weatherproof Housing: Ratings, Purging and Mounting Limits
TL;DR: The weatherproof enclosure for a Bently Nevada 3500 rack is the 3500/06, not the 3500/01 — 3500/01 is the…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Omron C6 Servo Launches in Europe: What Changes for 1S and Spares
Omron's C6 servo launched in Europe on 7 October 2026 with a 26-bit encoder, 3.5 kHz response and STO. What…