Emerson A6824-R
A6824R/A6824-R ModBus and Rack Interface Module
Genuine surplus Emerson A6824-R ModBus and Rack Interface Module for AMS 6500 systems, verified and ready to ship from Autronexa.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Data bits | 8 |
|---|---|
| Default IP address | 192.168.255.1 |
| Subnet mask | 255.255.255.0 |
| Parity | Even |
| Stop bit | 1 |
| Width | 19.98mm (0.79in) (4 TE) |
| Height | 128.4mm (5.055in) (3 HE) |
| Length | 160mm (6.300in) |
| Net weight | app 320g (0.705lbs) |
| Space requirement | 1 slot |
Description
The Emerson A6824-R is a ModBus and Rack Interface Module for AMS 6500 machinery protection systems. It reads parameters from all AMS 6500 modules and outputs them via ModBus TCP/IP and/or ModBus RTU, giving operators machinery health data inside the control environment. For maintenance and procurement teams supporting critical rotating machinery, a genuine surplus or refurbished unit keeps the protection rack complete without waiting on OEM lead times.
What the A6824-R Does in an AMS 6500 Rack
This unit occupies one slot and works alongside other AMS 6500 monitors to build a complete API 670 machinery protection monitor. It powers local graphical displays at the protection rack for machine and instrumentation readout. Either ModBus TCP/IP or ModBus RTU can be configured, or both can run simultaneously for redundant paths. Data types include speed, vibration (1/2x, 1x, etc.), gap value, alarm state, channel OK and phase. The module is part of the PlantWeb and AMS software environment, so maintenance personnel can use predictive and performance diagnostic tools to identify machine malfunctions early.

Key Interface and Environmental Specifications
This unit is built for reliable plant-floor service. ModBus RTU serial settings are 19.2 kbaud, 8 data bits, even parity and 1 stop bit. The default IP address is 192.168.255.1 with subnet mask 255.255.255.0, and the Ethernet connection uses an RJ 45 socket, 10BaseT. A green LED confirms power supply OK. The module carries IP 00 protection, while the front plate is rated IP 21 per DIN 40050. Operating temperature is 0° to 65°C (32° to 149°F), storage temperature is -30° to 85°C (-22° to 185°F), and relative humidity is 5 to 95%, non-condensing. Power consumption is max. 5 W. The card measures 19.98mm wide, 128.4mm high and 160mm long, with a net weight of approximately 320g. One slot is required, and 14 modules fit into each 19-inch rack.

Why Genuine Surplus Makes Sense for This Module
When a rack interface module fails, the priority is restoring machinery health data to the control room. Autronexa supplies genuine surplus and refurbished Emerson automation components with verified condition and clear lead times. Each unit is checked against OEM datasheet markings and part-number cross-reference, then functionally verified by our sourcing team. Because these modules are often requested for existing AMS 6500 installations, surplus stock can be a practical alternative to waiting on factory lead times. Our team also provides technical sourcing help across Allen-Bradley, Bently Nevada, Siemens and Schneider systems, so you can confirm revision and accessory compatibility before ordering. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this a genuine Emerson A6824-R or a clone?
Autronexa verifies every A6824-R against OEM datasheet markings and part-number cross-reference. We supply genuine surplus and refurbished units, not grey-market copies.
What condition will the A6824-R arrive in?
Units are supplied as refurbished by default, tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact Autronexa for the specific condition grade of current stock.
How fast can you ship the A6824-R?
Lead time depends on current verified stock. Contact Autronexa with your part number for current availability and lead time before ordering.
Does the A6824-R work with both ModBus TCP/IP and ModBus RTU?
Yes. The module can be configured for either ModBus TCP/IP or ModBus RTU, or both can be used simultaneously for redundant paths.
Related & compatible parts
Emerson
A6312
Genuine surplus Emerson A6312 dual-channel speed and key monitor for AMS 6500 systems, verified condition and ready to…
Emerson
EZ1080-12-00-010
Genuine surplus Emerson EZ1080-12-00-010 8mm eddy current sensor with M10x1 threads and 1m cable, verified for turbomachinery displacement…
Emerson
EZ1080-16-11-010
Genuine surplus Emerson EZ1080-16-11-010 8mm eddy current sensor with 160mm case, M10x1 threads and 1m cable — verified…
Emerson
A6120
Genuine surplus Emerson A6120 two-channel seismic vibration monitor for CSI 6500 racks — verified condition, practical lead times.
News & guides for Emerson
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…
Motion Control Precision: Servo Loops, Fieldbus Jitter, AI
Motion control precision depends on servo loop rates, fieldbus cycle times and jitter, sensor latency and mechanics. AI sits above…
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Bently Nevada 3500/06 Weatherproof Housing: Ratings, Purging and Mounting Limits
TL;DR: The weatherproof enclosure for a Bently Nevada 3500 rack is the 3500/06, not the 3500/01 — 3500/01 is the…