ABB DI818
Digital Input Module
Genuine surplus ABB DI818 digital input module — 32 channels, 24 V d.c., two isolated groups. Verified condition, ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Article number | 3BSE069052R1 |
|---|---|
| Number of channels | 32 |
| Signal type | Current sinking |
| Input voltage range, "0" | -30 .. +5 V |
| Input voltage range, "1" | 11 .. 30 V |
| Input impedance | 5.6 kΩ |
| Isolation | Groupwise isolated from ground, groups of 16 channels |
| Filter times (selectable) | 2, 4, 8, 16 ms |
| Power dissipation | Typ. 3.1 W |
| Operating temperature | 0 to +55 °C (+32 to +131 °F) |
Description
When a digital input module fails, every hour of downtime adds cost. The ABB DI818 digital input module delivers 32 channels for 24 V d.c. current-sinking signals, split into two isolated groups of 16 with voltage supervision. Autronexa supplies genuine surplus and refurbished units, verified against OEM datasheet markings and functionally tested, so you get a practical replacement without OEM lead times.
What This Module Solves in an S800 System
The DI818 addresses a common integration pain point: dense field-signal acquisition without sacrificing diagnostic visibility. Each input channel includes current-limiting components, EMC protection, an input state LED, and an optical isolation barrier. The two groups are individually isolated from ground, and each carries one process voltage supervision input. If process voltage disappears, the module generates a channel error signal readable via ModuleBus. Filter times are selectable at 2, 4, 8, or 16 ms, letting you tune response to noisy field conditions. The module fits S800 mechanics and pairs with MTU types TU818, TU819, or TU830. Keying code EA helps prevent incorrect MTU mating.

Surplus Advantage: Verified Stock vs. OEM Wait
For a module this specific, OEM lead time can stall a maintenance window. Autronexa keeps genuine surplus and refurbished ABB S800 components in stock, and every unit is checked against OEM datasheet specifications and functionally verified by our sourcing team. That means you get a part with known condition, not an unknown-history pull. This unit is rated for 0 to +55 °C operating, with approvals issued for +5 to +55 °C, and carries CE marking plus marine certifications from ABS, BV, DNV, and LR. Corrosion protection meets ISA-S71.04: G3, and RoHS compliance follows DIRECTIVE/2011/65/EU. For buyers replacing a failed input card, surplus stock often shortens the path from diagnosis to restart.

Selection and Sourcing Guide
Before ordering, confirm your existing MTU type — TU818, TU819, and TU830 are the listed matches — and verify the keying code EA on the carrier. Check whether your application needs the full 32 channels or if a partial population is acceptable; this module provides all 32. Confirm the input voltage range suits your field devices: “0” is -30 to +5 V and “1” is 11 to 30 V. Also review the maximum field cable length of 600 meters (656 yards) against your installation layout. Autronexa can help cross-reference your current part number and confirm compatibility. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this a genuine ABB DI818, or a clone?
Autronexa verifies every unit against OEM datasheet markings and part-number cross-reference. This is a genuine ABB module, not a copy.
What condition will the DI818 arrive in?
Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available — contact us for current stock.
How fast can you ship the DI818?
Lead time depends on current stock. Contact Autronexa for verified availability and shipping options.
Does the DI818 work with my existing MTU?
The DI818 is listed for use with MTU types TU818, TU819, and TU830. Confirm your MTU model and keying code EA before ordering.
Is the DI818 still supported by ABB?
Lifecycle status is not stated in our data. Contact Autronexa to verify OEM support status and availability.
Related & compatible parts
ABB
DI801
Genuine surplus ABB DI801 digital input module — 16 channels, 24 V d.c., S800 I/O. Verified condition, tested,…
ABB
AI910S
Genuine surplus ABB AI910S analog input module for S900 I/O — 4-channel 4...20 mA, ATEX Zone 1, verified…
ABB
CI858
Genuine surplus ABB CI858 DriveBus interface for AC 800M — verified, tested, and ready to ship with clear…
ABB
DI524
Genuine surplus ABB DI524 S500 digital input module — 32 DI at 24VDC, verified condition and faster lead…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…