Technical specifications
| Channels | 8 isolated |
|---|---|
| Maximum voltage | 250 V |
| Maximum current per channel | 3 A |
| Wire size (solid) | 0.2 – 6 mm² |
| Wire size (stranded) | 0.2 – 4 mm², 24 – 10 AWG |
| Recommended torque | 0.5 – 0.6 Nm |
| Stripping length | 7 mm |
| Operating temperature | 0 to +55 °C |
| Protection class | IP20 |
Description
When an S800 I/O station needs its ModuleBus extended to additional I/O modules, the ABB TU831V1 Extended MTU is the interface that carries the bus and sets the address for each slot. Maintenance teams and system integrators choose genuine surplus or refurbished units to keep existing ABB installations running without waiting on OEM lead times.
What This Extended MTU Does in an S800 I/O Station
The TU831V1 is a terminal unit for ABB S800 I/O. It distributes the ModuleBus to the I/O module and to the next MTU, and it generates the correct address for the I/O module by shifting outgoing position signals. This unit supports up to 8 isolated channels, with a maximum rated voltage of 250 V and 3 A per channel. It mounts on a standard DIN rail and includes a mechanical latch that locks the unit to the rail for grounding. Mechanical keying prevents insertion of the wrong I/O module, which protects both the terminal unit and the module during maintenance swaps. The extended type provides a greater connection area for larger wires, and process connections total 16 (2 terminals per channel).

Wiring and Installation Details That Matter
Field wiring is where most startup delays occur. This terminal unit accepts solid wire from 0.2 to 6 mm² and stranded wire from 0.2 to 4 mm² (24–10 AWG). The recommended torque is 0.5–0.6 Nm, and the stripping length is 7 mm. The dielectric test voltage is 2000 V a.c. The unit is rated IP20 according to IEC 60529 and operates from 0 to +55 °C, with approvals issued for +5 to +55 °C. Corrosion protection meets ISA-S71.04: G3, and RoHS compliance is EN 50581:2012. This unit is designed for use with I/O modules DI820, DI821, DO820, and DO821.

Why Genuine Surplus Makes Sense for This Module
ABB S800 I/O remains widely installed, but sourcing specific terminal units through OEM channels can involve extended lead times. Autronexa stocks genuine surplus and refurbished unit units that are tested against OEM datasheet specifications and functionally verified by our sourcing team. You get a verified part with clear lead times, not a grey-market clone. For maintenance managers keeping a line running, that difference matters. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this ABB TU831V1 a genuine unit or a clone?
Autronexa verifies every TU831V1 against OEM datasheet markings and part-number cross-reference. We supply genuine surplus and refurbished units only.
What condition will the TU831V1 arrive in?
Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact us for current condition details on specific stock.
How fast can you ship the TU831V1?
Lead time depends on current stock. Contact Autronexa for verified availability and lead time before ordering.
Which I/O modules work with this terminal unit?
The TU831V1 is designed for use with ABB I/O modules DI820, DI821, DO820, and DO821. Mechanical keying prevents insertion of the wrong module.
Is the TU831V1 still supported by ABB?
Please verify current lifecycle status and availability with Autronexa before ordering. We can confirm OEM support status for your specific unit.
Related & compatible parts
ABB
TB840A
Genuine surplus ABB TB840A Modulebus Cluster Modem — fiber optic interface for S800 I/O redundancy, verified and ready…
ABB
TB805
Genuine surplus ABB TB805 ModuleBus Cable Adaptor for extending ModuleBus across DIN rails. Verified condition, ready to ship.
ABB
ACS880-01-430A-3
Genuine surplus ABB ACS880-01-430A-3 drive, 250 kW / 430 A, verified condition and ready for sourcing.
ABB
TU841
Genuine surplus ABB TU841 termination unit for non-redundant I/O — verified condition, practical lead times, sourcing support from…
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…