Genuine surplus ABB TZIDC positioner, double-acting fail-safe, 4–20 mA, IP 65. Verified condition and sourcing support from Autronexa.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Input signal | 4...20 mA, two-wire |
|---|---|
| Output / safe position | Double acting, fail safe |
| Supply pressure | 1.4 ... 6 bar (20 ... 90 psi) |
| Air consumption | < 0.03 kg/h / 0.015 scfm (independent of supply pressure) |
| Housing protection | Aluminum, IP 65 / NEMA 4X |
| Pneumatic connections | G 1/4 or 1/4-18 NPT |
| Cable connection | Thread 1/2-14 NPT |
| Weight | 1.7 Kg |
Description
When a control valve positioner fails, the whole loop goes blind and production suffers. The ABB V18345-2010421001 TZIDC electro-pneumatic positioner is the intelligent, configurable unit that keeps valve travel accurate and reliable. Autronexa supplies genuine surplus and refurbished units, verified against OEM datasheet markings, so you get a trustworthy replacement without the OEM lead time or list price.
What This TZIDC Variant Delivers on the Plant Floor
This is not a generic positioner. The V18345-2010421001 is configured for double-acting actuators with fail-safe action: if electrical power is lost, output 1 depressurizes and the valve moves to its safe position, while the second output pressurizes to drive the actuator positively. That behavior is critical in emergency shutdown or trip scenarios where a valve must go to a known state. The unit accepts a 4–20 mA two-wire input with a connector plug for an LKS adapter, and the aluminum housing carries IP 65 / NEMA 4X protection, so it stands up to washdowns and dusty plant environments. A mechanical position indicator gives local feedback at a glance. Because this variant ships without explosion protection, it suits unclassified areas where a robust, intelligent positioner is needed.

Why Genuine Surplus Beats Waiting for a New Build
OEM lead times for configured positioners can stretch weeks, and a stalled control valve costs far more than the part. Autronexa stocks surplus and refurbished TZIDC units that are tested against OEM datasheet specifications and functionally verified by our sourcing team. You get the genuine article — not a clone — with clear condition notes and current availability. For maintenance teams managing obsolescence or urgent breakdowns, this is the practical route: genuine parts, verified, ready to ship. We also help you confirm the exact revision and option set before dispatch, so the replacement matches your actuator and control scheme.

Sourcing Checklist for This Positioner
Before you order, verify the actuator type (double-acting, fail-safe), the input signal (4–20 mA two-wire), and the connection threads (cable 1/2-14 NPT, air 1/4-18 NPT). Also confirm whether your loop uses the LKS adapter plug, since this unit includes that connector. If you need analog or digital position feedback, check whether the plug-in module is present — this variant includes analog feedback (4–20 mA) but no mechanical digital feedback kit. Autronexa can cross-reference your existing nameplate and provide a verified condition report. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this a genuine ABB V18345-2010421001, or a clone?
Autronexa verifies every unit against OEM datasheet markings and part-number cross-reference. We supply genuine surplus and refurbished ABB positioners, not grey-market copies.
What condition will the positioner arrive in?
Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available — ask for a condition report.
How fast can you ship the V18345-2010421001?
Lead time depends on current stock. Contact Autronexa for verified availability and lead time; surplus units typically ship faster than OEM new-build.
Does this unit work with a double-acting actuator?
Yes — this variant is configured for double-acting, fail-safe operation. On power loss, output 1 depressurizes and the second output pressurizes to move the valve to its safe position.
Is the ABB TZIDC still supported by the manufacturer?
Lifecycle status varies by configuration. Contact Autronexa to verify OEM support status and availability before ordering.
Related & compatible parts
ABB
PM863K02
Genuine surplus ABB PM863K02 High Integrity CPU board for AC 800M — verified, tested, and ready to ship…
ABB
TU840
Genuine surplus ABB TU840 termination unit for redundant TB840/TB840A ModuleBus systems — verified condition, practical lead times.
ABB
CI867K01
Genuine surplus ABB CI867K01 Modbus TCP interface with TP867 baseplate — verified condition, faster than OEM lead times.
ABB
TB820V2
Genuine surplus ABB TB820V2 Cluster Modem — fiber optic ModuleBus interface, verified condition, faster lead time than OEM.
News & guides for ABB
ABB Buys Rotork: What the $5.5B Deal Means for Actuator Spares
ABB's $5.5 billion cash offer for Rotork, part-funded by the SoftBank robotics divestment, moves the group deeper into mission-critical flow…
Emerson Q4 FY2026: LNG Sales Up 68%, Semiconductor Up 43%, Software ACV at $1.7B
Emerson closed FY2026 with 7% sales growth and 14% underlying order growth. We verify what the 68% LNG, 43% semiconductor,…
Siemens MIS: A Specification Walkthrough for the Pre-Engineered Microgrid Switchboard
Siemens MIS published ratings, one-line interface responsibilities, UL 891 and UL 3141 scope, and what factory testing does and does…
Murata’s SWL RF Test Connector: What the 40% Claim Actually Covers
Murata Manufacturing announced on 29 October 2026 that its SWL series of RF and microwave coaxial connectors with a built-in…
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…