Bently Nevada 3500/20 RIM: Slot 1, I/O Modules, OK Relay

Onshore gas production platform with Bently Nevada machinery protection and condition monitoring systems

TL;DR: The Bently Nevada 3500/20 Rack Interface Module (RIM) is the primary interface to a 3500 rack. It carries the proprietary protocol used to configure the rack and retrieve machinery information, and it must sit in slot 1, next to the power supplies. A rear I/O module adds RS-232/RS-422, modem or Data Manager ports, and RS-422 is the only rack-to-rack link.

Sourcing pages often describe the 3500/20 as a communication card. Inside a 3500 system it is also the rack configuration gateway and the source of the system OK relay, so its slot position and rear I/O choice affect commissioning. The statements below are checked against the Baker Hughes 3500/20 datasheet 141531 Rev. C, the RIM Operation and Maintenance Manual 129768-01 Rev. F, the 3500/05 rack specification 141525 and the 3500 hardware and software manual 128158-01.

What is the Bently Nevada 3500/20 Rack Interface Module?

The 3500/20 is the primary interface to the 3500 rack. It supports a Bently Nevada proprietary protocol used to configure the rack and retrieve machinery information. It also provides the connections for compatible external communication processors – TDXnet, TDIX and DDIX. Bently Nevada states that the RIM is not part of the critical monitoring path and has no effect on normal monitoring operation.

One RIM is required per rack. The front panel provides an RS-232 configuration port, a rack reset button, a 63-position rack address switch and a RUN/PROGRAM keylock. The address switch identifies the rack on a network, while the keylock blocks configuration changes in RUN and allows local or remote configuration in PROGRAM.

The RIM and the 3500/22M Transient Data Interface (TDI) are the two modules that can fill slot 1. The wider rack layout is covered in the Bently Nevada 3500 rack architecture and slot layout guide.

Why must the 3500/20 RIM be installed in slot 1?

Bently Nevada specifies that the RIM must be located in slot 1 of the rack, next to the power supplies. The 3500/05 rack reserves the far-left positions for the power supplies and the RIM. Neither the datasheet nor the O&M manual defines an alternative slot, so any other position is outside the specified configuration.

The 3500/05 rack has 14 module slots in the full-size version and 7 in the mini-rack. The power supplies and the RIM occupy the far-left positions; the remaining slots accept monitors, relay modules, Keyphasor modules and communication gateways. The 3500/15 power supply modules sit immediately to the left of slot 1, which is why the RIM position is described as “next to the power supplies.”

Slot 1 is shared with the TDI, not duplicated. Bently Nevada states that every 3500 rack requires one TDI or RIM, which always occupies slot 1. A rack with a TDI does not also carry a separate 3500/20, and a rack with a 3500/20 does not carry a TDI.

The public documents make slot 1 mandatory but do not print a specific error message for a misplaced RIM. Treat the wording as a hard installation requirement and verify the physical position before power is applied. A RIM in another slot is outside the documented configuration, and the configuration and data path described in the manual assume slot 1.

Which I/O modules can be fitted to the 3500/20?

Two rack interface I/O modules are available: the RS-232/RS-422 module (125768-01) and the Modem module (135031-01). A third rear option, the Data Manager I/O module (125760-01), adds two ports for TDIX or DDIX processors. The I/O module occupies one full-height rear slot behind or above the RIM.

Rear module Spare part Ports and protocol Maximum rate Cable length Typical use
RS-232/RS-422 I/O 125768-01 9-pin host connector; RS-232, RS-422 or external modem 38.4 kbaud RS-232 30 m (100 ft); RS-422 1200 m (4000 ft); external modem typical 3 m, per modem vendor Host software, local RS-232, rack-to-rack RS-422
Modem I/O 135031-01 Hayes AT-compatible; telephone jack 14.4 kbaud 2.1 m (7 ft) Dial-up access to a remote rack
Data Manager I/O 125760-01 Two sets of ports to TDIX or DDIX processors 9600 baud only 3 m (10 ft) Static and dynamic data to external communication processors

Ordering code B selects the rear module. B01 is the I/O module with built-in modem; B02 is the I/O module with the RS-232/RS-422 interface. The Data Manager I/O module is a separate item with its own full-height rear slot, not a third B option in the RIM ordering table.

The RS-232/RS-422 module carries a switch that selects RS-232 or RS-422 on the host connector. RS-232 is limited to 30 m, RS-422 reaches 1200 m, and an external modem follows the modem vendor’s cable limit, typically 3 m. The modem module is a self-contained Hayes AT-compatible unit rated to 14.4 kbaud and 2.1 m to the telephone jack.

The Data Manager module is the route for transient and dynamic data. It presents two sets of ports at a fixed 9600 baud and a 3 m cable limit, and it connects Bently Nevada Transient Data Interface External (TDIX) or Dynamic Data Interface External (DDIX) processors to the rack. The front-panel RS-232 port is separate: it is RS-232 only, 38.4 kbaud maximum, 30 m maximum, and configures or retrieves data from only that rack.

How are multiple 3500 racks daisy-chained over RS-422?

Rack-to-rack links use RS-422 only. The HOST connector on the I/O module connects to the previous rack, and the RACK connector feeds the next rack; the chain ends at the host computer. The rack connector is rated to 38.4 kbaud over 1200 m (4000 ft).

The HOST connector accepts RS-232, RS-422 with a converter, or an external modem when it serves a local host. In a daisy chain, the same connector is the input from the previous rack, and Bently Nevada specifies RS-422 ONLY for that link. The RACK connector is also RS-422 only. The switch on the I/O module connected to the host computer must be in the RS-422 position, and the chain rate is set by the link between the host computer and the first RIM.

Bently Nevada lists two rack-to-rack cables: 130122 with PVC insulation and 131107 with Teflon insulation, both ordered by length from 3 m to 152 m. Runs longer than 152 m use the 130121 extension cable. The host-to-rack RS-422 cable is 132632, and the converter-to-rack cable is 130120.

Termination is not fully published. The datasheet lists internal termination headers (00580441, 3-position; 00580436, 6-position) among the module spares, but it gives no field terminating-resistor value and no maximum number of racks in a chain. Confirm both points against the current manual before wiring a long chain rather than adding an assumed resistor.

What causes the 3500/20 OK relay to change to NOT OK?

The OK relay is normally energized and changes state when the rack is not OK. Removing the RIM, inserting a module during self-test, a module hardware or configuration fault, a slot ID failure, a transducer fault (except Keyphasor), a communication failure or a configured security violation all drive it to NOT OK.

Trigger Detail from the RIM manual
RIM removed Removing the Rack Interface Module from the 3500 rack
Module inserted Plugging a module into the rack, during self-test
Transducer fault A transducer going not OK, except a Keyphasor transducer
Module hardware failure Hardware failure within a module
Configuration failure Configuration failure in the rack
Slot ID failure Slot ID failure
Any module fault Any module in the rack that has detected a fault
Communication failure Communication failure with any module
Security options If configured and the condition is met: rack address changed while the RIM is in RUN mode; any module inserted or removed; key switch changed from RUN to PROGRAM

The relay is normally energized, and the user selects either an OPEN or a CLOSED contact to annunciate NOT OK. The de-energized state is therefore the NOT OK state, which also makes a power loss visible to the annunciator. The contact is rated to 5 A at 24 Vdc or 120 Vac, 120 W or 600 VA switched power, and arc suppressors are fitted to the normally closed contacts.

The RIM’s own OK status has two additional failure entries: node voltage failure and OK relay coil check failure. The manual adds that if the module OK status goes not OK, the system OK relay on the rack interface I/O module is driven not OK. In other words, the RIM does not only report its own health; it passes the rack-level fault to the same relay.

What do the front-panel controls and external contacts do?

The front panel provides an RS-232 configuration port, a rack reset button, a 63-position rack address switch and a RUN/PROGRAM keylock. Three external inputs – trip multiply, alarm inhibit and rack reset – are dry contacts to common, drawing less than 1 mA dc.

The rack reset button clears latched alarms and Timed OK Channel Defeat in the rack, and performs the same function as the Rack Reset contact on the I/O module. The key can be removed in either position: RUN locks out configuration changes, while PROGRAM permits local or remote configuration. The external contacts are dry-contact inputs, so the site supplies the switching device and the common reference.

Where does the I/O module mount in rack, panel and bulkhead formats?

The rack interface I/O module must be installed behind the RIM in a rack-mount or panel-mount rack, and above the RIM in a bulkhead rack. Panel and rack formats give rear access to wiring and I/O; bulkhead format gives front access because the rear of the rack faces the wall.

Rack format Wiring and I/O access I/O module position Notes
Panel mount Rear of rack Behind the RIM Clamps into a rectangular panel cutout
Rack mount Rear of rack Behind the RIM Mounts on 19-inch EIA rails
Bulkhead mount Front of rack Above the RIM Rack fixed against a wall or panel; not available in the mini-rack

The RIM main board takes one full-height front slot and the rack interface I/O module takes one full-height rear slot. The Data Manager I/O module also needs one full-height rear slot. In a bulkhead rack the rear of the rack is against the wall, so all wiring and I/O work happens from the front; this is also why the 3500/06 weatherproof housing is not compatible with the bulkhead option, as covered in the 3500/06 weatherproof housing guide.

Standard or TMR: which 3500/20 variant do you need?

Standard monitoring uses the standard RIM (125744-02). A Triple Modular Redundant rack requires the TMR RIM (125744-01), which compares three redundant monitor outputs and flags a monitor whose data departs from the other two beyond a configured percentage.

The ordering code is 3500/20-AXX-BXX-CXX. A01 is the standard RIM and A02 is the TMR RIM; B01 is the modem I/O module and B02 is the RS-232/RS-422 I/O module; C00 is no agency approval and C01 is CSA/NRTL/C. The TMR RIM performs monitor channel comparison and places an event in the System Event List when a monitor is flagged.

The RIM consumes 4.75 W typical. Bently Nevada rates the RIM and the RS-232/RS-422 I/O module from -30 °C to +65 °C, and the modem I/O module from 0 °C to +50 °C, with 95% non-condensing humidity. The RIM measures 241.3 x 24.4 x 241.8 mm and weighs 0.91 kg; the rear I/O modules measure 241.3 x 24.4 x 99.1 mm and weigh 0.45 kg.

What are the most common 3500/20 installation mistakes?

The recurring errors are placing the RIM outside slot 1, mounting the I/O module in the wrong rear position, trying to daisy-chain racks over RS-232, fitting a standard RIM in a TMR rack, and assuming the OK relay is normally open. Each one contradicts a published requirement rather than a site preference.

  • RIM outside slot 1. The datasheet and manual both say slot 1, next to the power supplies. No alternative is published.
  • I/O module in the wrong position. Rack and panel formats need it behind the RIM; a bulkhead rack needs it above the RIM.
  • RS-232 between racks. The RACK connector and the previous-rack link on the HOST connector are RS-422 only.
  • Standard RIM in a TMR rack. TMR configurations require the TMR RIM, 125744-01, not the standard 125744-02.
  • Assuming a normally open OK relay. The relay is normally energized; the user chooses OPEN or CLOSED to represent NOT OK, so the de-energized state is the alarm state.

Two more checks belong on the commissioning list. Confirm that the rear module matches the ordering code, because a modem module and an RS-232/RS-422 module look similar from the front but serve different links. Then confirm the rack address and keylock position, since both appear in the security-related NOT OK conditions when those options are configured.

Frequently asked questions

Can the 3500/20 RIM be installed in a slot other than slot 1?

No alternative slot is published. Bently Nevada states that the RIM must be located in slot 1 of the rack, next to the power supplies. The 3500/05 rack reserves the far-left positions for the power supplies and the RIM, and the manual does not define another location. Verify the physical slot before power is applied.

Do I need a rear I/O module for the 3500/20?

The published ordering table has no “no I/O” code: option B selects either the modem I/O module (B01) or the RS-232/RS-422 I/O module (B02). The Data Manager I/O module is a separate rear module with its own slot. The front-panel RS-232 port is part of the RIM and is separate from the rear module.

Can RS-232 be used to daisy-chain 3500 racks?

No. The RACK connector is RS-422 only, and the HOST connector uses RS-422 only when it connects to the previous rack. RS-232 is available for a local host connection, but it is not a rack-to-rack link. The switch on the I/O module at the host must be in the RS-422 position.

What is the maximum RS-422 distance between 3500 racks?

Bently Nevada rates the rack connector to 1200 m (4000 ft) at 38.4 kbaud maximum. Rack-to-rack cables 130122 and 131107 are ordered up to 152 m, and longer runs use the 130121 extension. The maximum number of racks in one chain is not published in the datasheet.

What happens to the OK relay when the RIM is removed?

The relay is normally energized, so removing the RIM de-energizes it and produces the NOT OK state. The manual lists removing the Rack Interface Module from the rack as one of the conditions that cause the OK relay to go NOT OK. The same applies when a module is plugged in during self-test.

Is the OK relay normally open or normally closed?

It is normally energized, and the user selects either an OPEN or a CLOSED contact to annunciate NOT OK. The de-energized state is the NOT OK state, so loss of power also produces the alarm condition. The contact is rated to 5 A at 24 Vdc or 120 Vac, 120 W or 600 VA.

Where does the I/O module go in a bulkhead rack?

Above the RIM. In a rack-mount or panel-mount rack the I/O module goes behind the RIM, but a bulkhead rack is fixed against a wall or panel, so wiring and I/O modules are reached from the front. The bulkhead format is not available in the 3500/05 mini-rack.

What is the difference between the standard and TMR RIM?

The standard RIM is 125744-02 and serves standard monitoring. The TMR RIM is 125744-01 and is required for Triple Modular Redundant configurations; it compares three redundant monitor outputs and flags a monitor whose data departs from the other two beyond a configured percentage, placing an event in the System Event List.

Where these figures come from

Module description, slot 1 requirement, I/O types, baud rates, cable lengths, relay rating, dimensions, temperature limits and ordering codes: Baker Hughes 3500/20 Rack Interface Module datasheet 141531 Rev. C. OK relay conditions, module status conditions, connector roles, external contacts and I/O module mounting positions: Bently Nevada 3500/20 Rack Interface Module Operation and Maintenance Manual 129768-01 Rev. F. Rack formats, slot count and far-left reserved positions: 3500/05 System Rack specification 141525. I/O module installation at the back or top of the rack: 3500 Monitoring System Computer Hardware and Software Manual 128158-01.

Where the public documents are silent – a field termination resistor value, a maximum rack count per RS-422 chain, or a specific error message for a RIM outside slot 1 – the article says so instead of filling the gap with a supplier claim. Confirm those points against the current manual before wiring or commissioning.

Related reading

Last checked 24 November 2026 against datasheet 141531 Rev. C and O&M manual 129768-01 Rev. F. Confirm the current revision with Baker Hughes before ordering.