MTL Proximity Probes & Sensors
MTL MTL4015
Switch or proximity detector located
Genuine surplus MTL4015 switch/proximity detector for hazardous areas, with dual relay outputs and verified condition from Autronexa.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Voltage applied to sensor | 7.0–9.0V dc from 1kΩ |
|---|---|
| Output threshold (closed) | >2.1mA (<2kΩ) in sensor circuit |
| Output threshold (open) | 10kΩ) in sensor circuit |
| Hysteresis | 200µA (650Ω) nominal |
| Response time | 2ms maximum |
| Contact rating | 10W, 0.5A, 35V (dc) |
| Contact life expectancy | 106 operations at maximum load |
| Isolation | 250V ac between safe and hazardous area circuits |
Description
The MTL4015 is an MTL switch or proximity detector interface that lets a sensor in a hazardous area control two safe-area relay outputs, so one sensor status can feed both control and shutdown systems. For maintenance and procurement teams, a verified surplus unit keeps a critical interlock path available without waiting on a full OEM lead time.
What the MTL4015 Does in a Safety Loop
The module applies 7.0–9.0V dc from 1kΩ to the sensor and closes its outputs when sensor current exceeds 2.1mA, opening them below 1.2mA. That hysteresis of 200µA (650Ω) nominal keeps output state stable near the trip point, which reduces nuisance switching and the labour cost of repeated resets. Because the two relay outputs are independent, one sensor can serve a control system and a separate shutdown path, avoiding the cost of a second detector and its associated wiring.

Technical Specs That Affect Operating Cost
The relay contact rating is 10W, 0.5A, 35V (dc), and contact life expectancy is 106 operations at maximum load. Sizing loads within that rating protects relay life and avoids premature replacement cost. Response time is 2ms maximum, so the loop reacts quickly to a sensor state change. Built-in line fault detection opens the output if input current falls below 100µA or rises above 6.5mA, flagging broken or shorted lines before they become unplanned downtime. Reactive loads must be adequately suppressed, and switch-type sensors need resistors or LFD disabled to prevent false triggering.

Why Genuine Surplus Fits This Module
Autronexa supplies genuine surplus and refurbished automation components, and each unit is verified against OEM datasheet markings before dispatch. Refurbished units are tested against the published specifications and functionally verified by our sourcing team. For a module that protects a hazardous-area interface, that verification matters more than a low price alone. Clear lead times and practical sourcing help across Allen-Bradley, Bently Nevada, Siemens and Schneider let you plan the replacement without holding excessive spares. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this MTL4015 a genuine MTL unit or a clone?
Autronexa verifies each MTL4015 against OEM datasheet markings and part-number cross-reference before it is listed, so you receive a genuine part rather than a copy.
What condition will the MTL4015 arrive in?
Units are supplied as genuine surplus or professionally refurbished, tested against the published specifications and functionally verified by our sourcing team.
How fast can you ship the MTL4015?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability.
Does the MTL4015 support two separate safe-area loads?
Yes. The MTL4015 provides two safe-area relay outputs, so one hazardous-area sensor can feed two separate systems such as control and shutdown.
Related & compatible parts
MTL
MTL4646Y
Genuine surplus MTL4646Y controller drives current/pressure converters with HART support and 800Ω load capacity. Verified condition, ready to…
MTL
SD16
Genuine MTL SD16 surge protection module with fuse disconnect, rated 16 Vdc and 250 mA — verified surplus…
MTL
SD07X
Genuine surplus MTL SD07X surge protection device with <1ns response time and low resistance, verified and ready for…
MTL
MTL4016
Genuine surplus MTL4016 interface: two channels, relay outputs, line fault detection, and hazardous-area certification for Zone 0/Div.1.
News & guides for MTL
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…
Motion Control Precision: Servo Loops, Fieldbus Jitter, AI
Motion control precision depends on servo loop rates, fieldbus cycle times and jitter, sensor latency and mechanics. AI sits above…
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Bently Nevada 3500/06 Weatherproof Housing: Ratings, Purging and Mounting Limits
TL;DR: The weatherproof enclosure for a Bently Nevada 3500 rack is the 3500/06, not the 3500/01 — 3500/01 is the…
Siemens Kärnten Netz Grid Software Contract: Scope and Limits
TL;DR: On 9 November 2026 Siemens announced a six-year software contract with Kärnten Netz GmbH (KNG), the Carinthian distribution system…