Technical specifications

Number of channels Two
Voltage applied to sensor 7.0 V – 9.0 V dc from 1 kΩ
Output thresholds Closed if >2.1 mA (10 kΩ)
Hysteresis 200 µA (650 Ω) nominal
Response time 2 ms maximum
Contact rating 10 W, 0.5 A, 35 V dc
Power requirement 50 mA at 24 V dc
Isolation 250 V ac between safe and hazardous area circuits
Line fault detection Outputs open if input current 6.5 mA

Description

The MTL4016 is a two-channel switch/proximity detector interface that lets sensors in hazardous areas control safe-area loads through reed relays. For engineers maintaining legacy safety or shutdown systems, a genuine surplus unit often restores operation faster than waiting on OEM lead times. Each channel accepts NAMUR-compliant sensor inputs and provides two independent relay outputs. The module suits applications where a single sensor status must feed two separate systems, such as control and shutdown. Independent phase-reversal switches on top allow alarm signalling for either sensor state, while built-in line fault detection (LFD) flags broken or shorted lines. Amber LEDs indicate output status per channel, and a green LED confirms power. With a 2 ms maximum response time and 10 W contact rating, the MTL4016 handles discrete signalling reliably. Autronexa supplies this unit as genuine surplus or refurbished stock, verified against OEM datasheet markings. Every unit is functionally tested, and our team can confirm current availability and condition before you commit. For plants running MTL4000-series interfaces, keeping a verified spare on hand reduces exposure to unplanned downtime.

What This unit Does in a Safety Loop

This unit sits between hazardous-area sensors and safe-area control equipment. It accepts two independent sensor inputs, each with a voltage of 7.0 V – 9.0 V dc from 1 kΩ, and drives two relay outputs per channel. Outputs close when sensor current exceeds 2.1 mA and open below 1.2 mA, with 200 µA hysteresis. This interface is typically used where a single proximity detector must signal both a control system and a separate shutdown system. Because the two channels are isolated to 250 V ac between safe and hazardous areas, cross-talk is minimized. The module also supports optional earth fault detection when linked to an MTL4220 earth leakage detector via terminals 3 and 6. For maintenance engineers, the top-mounted LEDs and phase-reversal switches simplify troubleshooting without removing field wiring.

Figure 1: Front view of the MTL MTL4016 Switches or proximity detectors located in showing its physical design and enclosure.

Technical Specifications That Matter

Three specs drive most selection decisions. First, the contact rating of 10 W, 0.5 A, 35 V dc defines the safe-area load the relay can switch; reactive loads must be adequately suppressed. Second, the 2 ms maximum response time suits discrete signalling but not high-speed pulsing. Third, line fault detection opens the output if input current falls below 100 µA (broken line) or rises above 6.5 mA (shorted line). Note that switch-type sensors require resistors to prevent false LFD triggering, or LFD can be disabled via top switches. The module operates from 24 V dc at 50 mA, with power dissipation of 1.2 W at 24 V.

Figure 2: Technical layout and connection details for the MTL MTL4016 Switches or proximity detectors located in.

Why Genuine Surplus Makes Sense for This Model

This unit is a mature interface, and OEM lead times for legacy MTL4000-series modules can stretch. Autronexa maintains verified surplus and refurbished stock, each unit tested against OEM datasheet specifications and functionally verified. That means you get a genuine unit with confirmed relay operation, LFD function, and LED indication. Our sourcing team works with Allen-Bradley, Bently Nevada, Siemens, Schneider and other major brands daily, so we understand the integration context. Contact Autronexa with your part number for verified condition and current availability. Surplus and refurbished, ready to ship.

📄 Download Datasheet: MTL4016-datasheet.pdf

Frequently asked questions

Is this a genuine MTL4016, or a clone?

Autronexa supplies only genuine MTL4016 units, verified against OEM datasheet markings and part-number cross-reference. Each unit is inspected and functionally tested before dispatch.

What condition will the MTL4016 arrive in?

Our default condition is refurbished: tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus units are also available; contact us for current grading.

How fast can you ship the MTL4016?

Lead time depends on current stock. Contact Autronexa for verified availability and lead time before ordering.

Does the MTL4016 work with NAMUR proximity detectors?

Yes. The MTL4016 is designed for NAMUR and DIN 19234 standard proximity detectors, with output thresholds of >2.1 mA to close and <1.2 mA to open.

Can I use the MTL4016 in a Zone 0 hazardous area?

The switch or proximity detector may be located in Zone 0, IIC, T6 hazardous area or Div.1, Group A, hazardous location, subject to the module's safety description and relevant approvals.

Related & compatible parts

MTL

ICC212

Genuine MTL ICC212 repeater power supply and isolating driver with three-port galvanic isolation, verified for smart transmitter loops.

In Stock

MTL

MTL3021

Genuine surplus MTL3021 switch/voltage change module for hazardous-area control, verified condition and practical sourcing support from Autronexa.

In Stock

MTL

MTL5541

Genuine surplus MTL5541 repeater power supply for 4-20mA transmitters in hazardous areas, with HART support and SIL2 capability.…

In Stock

MTL

MTL5041

Genuine surplus MTL5041 isolator: fully-floating 2-wire transmitter supply with 4 to 20mA repeat for safe-area loads. Verified condition,…

In Stock

News & guides for MTL

View all articles

Request a quote for this part

Part number: MTL4016

We reply within one business day.

MTL4016 Quote reply within 1 business day