MTL MTL5041
Located
Genuine surplus MTL5041 isolator: fully-floating 2-wire transmitter supply with 4 to 20mA repeat for safe-area loads. Verified condition, ready to ship.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Number of channels | One |
|---|---|
| Transmitter location | Zone 0, IIC, T4–6 hazardous area if suitably certified; Div. 1, Group A |
| Safe-area output signal range | 4 to 20mA |
| Safe-area over/under-range | 0 to 24mA |
| Safe-area load resistance | 0 to 1kΩ |
| Safe-area circuit output resistance | >2MΩ |
| Safe-area circuit ripple | <125µA peak-to-peak |
| Hazardous-area input signal range | 0 to 24mA (including over-range) |
| Transmitter voltage | 16.5V at 20mA |
| Supply voltage | 20 to 35V dc |
Description
The MTL5041 from MTL is a single-channel signal isolator that provides a fully-floating dc supply for a conventional 2-wire 4 to 20mA transmitter in a hazardous area and repeats the current into a floating safe-area circuit. Engineers specifying this unit get galvanic separation between field and control room without a separate power supply. Autronexa supplies genuine surplus and refurbished this unit units with verified condition and practical sourcing support.
What Does this unit Do in a 2-Wire Loop?
This unit sits between a hazardous-area transmitter and a safe-area load. It energises the transmitter with a floating supply and repeats the loop current in a separate floating circuit. The hazardous-area input accepts 0 to 24mA including over-range, while the safe-area output delivers 4 to 20mA with over/under-range of 0 to 24mA. A safe-area load resistance of 0 to 1kΩ suits most receiving instruments. The safe-area circuit output resistance exceeds 2MΩ, and ripple stays below 125µA peak-to-peak. A green LED gives power indication for quick loop checks.

Why Choose Genuine Surplus for This Isolator?
When an this unit fails, the priority is a verified replacement, not a long OEM lead time. Surplus and refurbished units are tested against OEM datasheet specifications and functionally verified by our sourcing team. That means you can confirm the 16.5V transmitter voltage at 20mA and the 4 to 20mA transfer before installation. For maintenance teams, genuine surplus removes the guesswork of grey-market clones. Autronexa focuses on Allen-Bradley, Bently Nevada, Siemens, Schneider and MTL families, so the sourcing conversation stays technical.

Which Installation Details Should You Verify?
This unit operates from a 20 to 35V dc supply and draws 70mA at 24V with a 20mA signal. Maximum power dissipation within the unit is 1.2W at 24V. Transfer accuracy at 20°C is better than 20µA, typically 5µA, with temperature drift below 1µA/°C. Response time settles to within 10% of final value within 250µs. The safety description is 28V, 300Ω, 93mA; Um = 250V rms or dc. Before ordering, confirm the hazardous-area certification suits your Zone 0, IIC, T4–6 or Div. 1, Group A location. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is the MTL5041 a genuine MTL unit or a clone?
Autronexa verifies every MTL5041 against OEM datasheet markings and part-number cross-reference before it enters stock. Units are genuine surplus or professionally refurbished, not grey-market copies.
What condition will the MTL5041 arrive in?
The MTL5041 is supplied as refurbished unless otherwise stated. Each unit is tested against OEM datasheet specifications and functionally verified by our sourcing team before dispatch.
How fast can you ship the MTL5041?
Lead time depends on current stock. Contact Autronexa with your MTL5041 requirement for verified condition and current availability.
Does the MTL5041 suit a Zone 0 hazardous-area transmitter?
Yes, the MTL5041 supports a transmitter located in Zone 0, IIC, T4–6 hazardous area if suitably certified, and Div. 1, Group A hazardous locations. Confirm your certification requirements with Autronexa.
Related & compatible parts
MTL
SD07R
Genuine MTL SD07R surge protector with 50MHz bandwidth. Verified surplus stock, tested and ready for your signal line…
MTL
MTL3021
Genuine surplus MTL3021 switch/voltage change module for hazardous-area control, verified condition and practical sourcing support from Autronexa.
MTL
MTL3013
Genuine surplus MTL3013 two-channel switch/proximity detector relay for hazardous-area sensors, verified and ready to ship from Autronexa.
MTL
MTL5541
Genuine surplus MTL5541 repeater power supply for 4-20mA transmitters in hazardous areas, with HART support and SIL2 capability.…
News & guides for MTL
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…
Motion Control Precision: Servo Loops, Fieldbus Jitter, AI
Motion control precision depends on servo loop rates, fieldbus cycle times and jitter, sensor latency and mechanics. AI sits above…
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Bently Nevada 3500/06 Weatherproof Housing: Ratings, Purging and Mounting Limits
TL;DR: The weatherproof enclosure for a Bently Nevada 3500 rack is the 3500/06, not the 3500/01 — 3500/01 is the…
Siemens Kärnten Netz Grid Software Contract: Scope and Limits
TL;DR: On 9 November 2026 Siemens announced a six-year software contract with Kärnten Netz GmbH (KNG), the Carinthian distribution system…