MTL Power Supplies

MTL MTL5541

Repeater Power Supply

Manufacturer: MTL Part Number: MTL5541

Genuine surplus MTL5541 repeater power supply for 4-20mA transmitters in hazardous areas, with HART support and SIL2 capability. Verified and ready to ship.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Number of channels One
Safe-area output signal range 4 to 20mA
Under/over-range 0 to 24mA
Safe-area load resistance @ 20mA 0 to 450Ω
Safe-area load resistance @ 24mA 0 to 360Ω
Transmitter voltage 16.5V at 20mA
Transfer accuracy at 20°C Better than 15µA
Communications supported HART (terminals 1 & 2 only)

Description

The MTL5541 from MTL is a repeater power supply that energises a conventional 2- or 3-wire 4/20mA transmitter in a hazardous area and repeats the current in a floating safe-area circuit. For maintenance and procurement teams, a verified surplus unit delivers the same isolated loop performance without the long lead times of a new OEM order.

What loop problems does this power supply solve?

When a transmitter sits in a Zone 0 or Division 1 area, the safe-area interface must supply isolated power and pass the measurement signal without adding noise or drift. This power supply addresses this with a fully-floating dc supply and a transmitter voltage of 16.5V at 20mA. Its transfer accuracy is better than 15µA at 20°C, and temperature drift stays below 0.8µA/°C. For HART 2-wire transmitters, the unit allows bi-directional communications signals superimposed on the 4/20mA loop current. The green LED provides power indication, so technicians can confirm the module is energised during fault-finding.

Figure 1: Front view of the MTL MTL5541 Repeater Power Supply showing its physical design and enclosure.

How does this power supply handle load and response requirements?

The safe-area output covers a signal range of 4 to 20mA, with under/over-range from 0 to 24mA. Load resistance depends on loop current: 0 to 450Ω at 20mA and 0 to 360Ω at 24mA. The safe-area circuit output resistance exceeds 1MΩ, and ripple is below 50µA peak-to-peak. Response is fast enough for dynamic processes, settling to within 10% of final value within 50µs. Maximum current consumption is 51mA at 24V with a 20mA signal, and power dissipation within the unit is 0.7W at 24V dc. These figures help you confirm the module suits your loop budget before installation.

Why choose genuine surplus for this power supply?

Autronexa supplies genuine surplus and refurbished this power supply units that are tested against OEM datasheet specifications and functionally verified by our sourcing team. This model is assessed for use in IEC 61508 functional safety applications: SIL2 capable for a single device (HFT=0) and SIL3 capable for multiple devices in safety redundant configurations (HFT=1). Because this power supply is a specialised interface for hazardous-area transmitters, sourcing a verified surplus unit can shorten the wait compared with a factory order. Contact Autronexa with your part number for verified condition and current availability.

Frequently asked questions

Is the MTL5541 a genuine MTL product or a clone?

Autronexa verifies every MTL5541 against OEM datasheet markings and part-number cross-reference. We supply genuine surplus and refurbished units, not grey-market copies.

What condition will the MTL5541 arrive in?

The MTL5541 is supplied as a refurbished unit, tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact Autronexa for current condition grading and availability.

Does the MTL5541 support HART communication?

Yes, the MTL5541 supports HART communication on terminals 1 and 2 only. For HART 2-wire transmitters, it allows bi-directional communications signals superimposed on the 4/20mA loop current.

What is the safe-area load resistance for the MTL5541?

The MTL5541 safe-area load resistance is 0 to 450Ω at 20mA and 0 to 360Ω at 24mA. The safe-area circuit output resistance is greater than 1MΩ.

Related & compatible parts

MTL

SD32R

Genuine surplus MTL SD32R surge protector with 32 Vdc nominal voltage, 400 mA nominal current, and high bandwidth…

In Stock

MTL

MTL3013

Genuine surplus MTL3013 two-channel switch/proximity detector relay for hazardous-area sensors, verified and ready to ship from Autronexa.

In Stock

MTL

MTL3021

Genuine surplus MTL3021 switch/voltage change module for hazardous-area control, verified condition and practical sourcing support from Autronexa.

In Stock

MTL

SLP07D

Genuine MTL SLP07D surge protection module for two process loops, with 20kA hybrid circuitry and verified surplus availability.

In Stock

News & guides for MTL

View all articles

Request a quote for this part

Part number: MTL5541

We reply within one business day.

MTL5541 Quote reply within 1 business day