Lenze I/O & Function Modules

Lenze E82CV551K4C

Replaced by a bare metal cooling plate connected to a separate customer-side

Manufacturer: Lenze Part Number: E82CV551K4C

Genuine surplus Lenze E82CV551K4C cold-plate inverter: 0.55 kW, 1.8 A at 8 kHz, 3/PE AC 320–550 V, IP20. Verified condition and clear lead times from Autronexa.

  • 12 Month
  • Refurbished
  • In Stock
Call us

Availability & pricing

Pricing is available on request — send an RFQ for a same-day quote.

5-15 days

Technical specifications

Rated motor power 0.55 kW typical (4-pole three-phase asynchronous motor)
Rated output current 1.8 A nominal at 8 kHz switching frequency
Max. output current 2.7 A for 60 s (1 min overload at Imax / 2 min base load at 75% Ir)
Supply voltage 3/PE AC 320 V -0% … 550 V +0%; 45 … 65 Hz
Operating temperature -10 … +55 °C (derated by 2.5%/°C above +40 °C)
Storage temperature -25 … +60 °C
Protection rating IP20
Built-in ports X3 control terminal strip (analog/digital I/O)
Communication expansion FIF slot for plug-in function modules (E82ZAF* family)

Description

The Lenze E82CV551K4C is a genuine surplus 8200 vector frequency inverter in cold-plate design, rated 0.55 kW with 1.8 A nominal output at 8 kHz. Maintenance and procurement teams choose verified surplus for this legacy model when OEM lead times stretch. Autronexa supplies tested units with clear condition notes and practical sourcing support.

What the Cold-Plate 8200 vector Inverter Does

The E82CV551K4C belongs to Lenze’s 8200 vector series, a workhorse family for three-phase asynchronous motor control. This special design replaces the standard heatsink with a bare metal cooling plate that mounts to a separate customer-side cooler. The inverter delivers V/f characteristic control (linear or quadratic) and sensorless vector control, with an output frequency range of -650 to +650 Hz. Rated motor power is 0.55 kW typical for a 4-pole motor, and rated output current is 1.8 A nominal at 8 kHz switching frequency. A periodic overload of 2.7 A for 60 s is available, following a 1 min overload at Imax and 2 min base load at 75% Ir cycle. An integrated brake transistor supports stopping duties. Built-in I/O covers 1 analog input, 1 analog output, 4 digital inputs, 1 digital output, and 1 relay output with changeover contact rated 250 V AC / 3 A.

Figure 1: Front view of the Lenze E82CV551K4C Replaced by a bare metal cooling plate connected to a separate customer-side showing its physical design and enclosure.

Technical Specs Breakdown

Three values matter most for integration. First, the supply accepts 3/PE AC 320 V -0% to 550 V +0% at 45 to 65 Hz, covering common industrial three-phase networks. Second, the cold-plate thermal path is defined: 30 W dissipated power loss, thermal resistance Rth ≤ 1.0 K/W between cooler and cooling medium, and a maximum permissible cooling-plate temperature of 75 °C. Third, the operating temperature range is -10 to +55 °C, derated by 2.5%/°C above +40 °C. The IP20 protection rating suits cabinet mounting. No fieldbus protocol is built in; the X3 control terminal strip handles analog and digital I/O, while the FIF slot accepts E82ZAF* plug-in function modules for communication expansion.

Figure 2: Technical layout and connection details for the Lenze E82CV551K4C Replaced by a bare metal cooling plate connected to a separate customer-side.

Surplus Advantage for This Legacy Model

Lenze lists the 8200 vector among its previous products, and the cold-plate special design is available on request. No drop-in same-order-code replacement exists; Lenze confirms the i950 emulates 8200 vector behaviour via the i950 PROFIBUS module and L_ICIP library. For a running machine, that makes genuine surplus the practical route. Autronexa verifies each unit against OEM datasheet markings and part-number cross-reference, then functionally tests it. You get a refurbished inverter with documented condition rather than an open-ended wait. Contact Autronexa with your part number for verified condition and current availability.

Selection and Sourcing Guide

Before ordering, confirm the cold-plate variant suits your cooling arrangement, because This unit has no heatsink. Check that your motor matches the 0.55 kW typical rating and 1.8 A nominal output. Verify the 3/PE AC 320–550 V supply is present at the installation point. If your system needs fieldbus, plan for an E82ZAF* function module in the FIF slot. Compare condition grades: surplus units are unused legacy stock, while refurbished units are tested against OEM datasheet specifications and functionally verified. Ask for the exact model string and any revision notes. Autronexa provides sourcing help across Allen-Bradley, Bently Nevada, Siemens, and Schneider lines as well, so one request can cover several spares. Please verify current lifecycle status and availability with Autronexa before ordering.

📄 Download Datasheet: E82CV551K4C-datasheet.pdf

Frequently asked questions

Is this E82CV551K4C a genuine Lenze unit or a clone?

Autronexa verifies every unit against OEM datasheet markings and part-number cross-reference. The E82CV551K4C is supplied as a genuine Lenze 8200 vector inverter, and condition notes accompany each offer.

What condition will the inverter arrive in?

Units are supplied refurbished by default, tested against OEM datasheet specifications and functionally verified by our sourcing team. Surplus unused stock may also be available; request the current condition grade with your part number.

How fast can you ship the E82CV551K4C?

Lead time depends on current verified stock. Contact Autronexa with your part number for verified condition and current availability, and we will confirm the shipping window.

Does the E82CV551K4C support fieldbus communication?

No protocol is built in. The X3 control terminal strip provides analog and digital I/O, and the FIF slot accepts E82ZAF* plug-in function modules for fieldbus expansion.

Is the Lenze 8200 vector still supported by the manufacturer?

Lenze lists the 8200 vector among its previous products, with the cold-plate special design available on request. Contact Autronexa to verify OEM support status and migration options for your application.

Related & compatible parts

Lenze

EPM-S404

Genuine surplus Lenze EPM-S404 analog input module with four RTD channels, 16-bit resolution, and verified condition from Autronexa.

In Stock

Lenze

E82CV152K2C

Genuine surplus Lenze E82CV152K2C cold-plate inverter, 1.5 kW, verified condition and ready to ship from Autronexa.

In Stock

Lenze

E94AZPS0034N

Genuine Lenze E94AZPS0034N passive installation backplane for 9400 Single Drive axis modules, without brake module. Verified surplus and…

In Stock

Lenze

ESMD113L4TXA

Genuine surplus Lenze ESMD113L4TXA frequency inverter: 11 kW, 400 VAC 3-phase, 27 A, PID control. Verified condition and…

In Stock

News & guides for Lenze

View all articles

Request a quote for this part

Part number: E82CV551K4C

We reply within one business day.

E82CV551K4C Quote reply within 1 business day