MTL MTL4013
Controlled
Genuine surplus MTL4013 two-channel unit for safe-area control from hazardous-area switches, with verified condition and fast sourcing from Autronexa.
- 12 Month
- Refurbished
- In Stock
Availability & pricing
Pricing is available on request — send an RFQ for a same-day quote.
5-15 days
Technical specifications
| Number of channels | Two |
|---|---|
| Operating frequency | dc to 5kHz |
| Maximum off-state voltage | 35V |
| Maximum off-state leakage current | 10µA |
| Maximum on-state current | 50mA |
| Maximum on-state voltage drop | [1+ (0.1 x current in mA)] V |
| Hysteresis | 200µA (650Ω) nominal |
| Isolation | 250V ac between safe and hazardous area circuits |
| Power requirement, Vs | 47.5mA at 24V dc |
| Power dissipation within unit | 1.15W at 24V |
Description
The MTL4013 is a two-channel unit that lets safe-area loads be controlled by switches or proximity detectors in hazardous areas. Autronexa supplies genuine surplus and refurbished units, verified for condition and ready to support your maintenance schedule.
What the MTL4013 Does in Your Control Loop
When a hazardous-area switch or proximity detector must drive a safe-area load, the interface has to pass a clean, logic-compatible signal without compromising isolation. This unit handles that task with two independent channels. Each channel accepts a sensor circuit and provides a solid-state output, so a detector in a Zone 0 or Div.1 location can control equipment in the safe area. Because the output is solid-state, there are no moving contacts to wear. The unit also suits positive displacement flowmeters and some turbine meters, where a reliable pulse output is needed. Two LEDs on top show power and switch status, which simplifies troubleshooting during routine checks.

Why Genuine Surplus Makes Sense for This Model
OEM lead times for interface modules can stretch when a line is down and a replacement is urgent. A genuine surplus or refurbished unit gives you a practical alternative. Each unit is tested against OEM datasheet specifications and functionally verified by our sourcing team before it ships. You get the same terminal layout and the same hazardous-area safety description, without waiting on a factory backlog. For maintenance managers, that means a verified spare can be on the shelf before the next shutdown. Autronexa focuses on genuine parts, verified, so you can compare condition and lead time directly.

Specs That Matter on the Plant Floor
This unit operates from dc to 5kHz, which covers the pulse rates of many flowmeter and detector applications. Each output is Zener-diode protected against inductive loads, a practical detail when driving relays or solenoids. The maximum on-state current is 50mA, and the maximum off-state voltage is 35V. Power consumption is modest: 47.5mA at 24V dc, with 1.15W dissipated at 24V. Isolation between safe and hazardous area circuits is rated at 250V ac. These figures help you confirm the module fits your loop without guesswork. If you need earth fault detection, This unit can be used with an MTL4220 earth leakage detector via the optional link terminals. Note that separate detectors are needed to maintain isolation between the two channels.
Sourcing the Right Condition for Your Spares Strategy
Before ordering, confirm the exact model and terminal function match your panel drawing. Check whether your application needs the optional earth fault link, and decide between surplus and refurbished condition based on your spares policy. Autronexa provides hands-on sourcing help across Allen-Bradley, Bently Nevada, Siemens, Schneider and more. Contact Autronexa with your part number for verified condition and current availability.
Frequently asked questions
Is this a genuine MTL MTL4013, or a clone?
Autronexa supplies genuine surplus and refurbished MTL4013 units. Each unit is verified against OEM datasheet markings and part-number cross-reference before it is listed.
What condition will the MTL4013 arrive in?
Units are supplied in refurbished condition by default, tested against OEM datasheet specifications and functionally verified by our sourcing team. Contact Autronexa for current condition details on specific stock.
How fast can you ship the MTL4013?
Lead time depends on current stock. Contact Autronexa with your part number for verified condition and current availability.
Does the MTL4013 work with an MTL4220 earth leakage detector?
Yes. Earth fault detection is enabled by connecting terminals 3 and 6 to an MTL4220 earth leakage detector. If you need to maintain isolation between the two channels, separate earth leakage detectors are required.
Related & compatible parts
MTL
SD32T3
Genuine MTL SD32T3 surge protection device with 3-terminal configuration and 10-year warranty. Verified surplus and refurbished units from…
MTL
MTL3021
Genuine surplus MTL3021 switch/voltage change module for hazardous-area control, verified condition and practical sourcing support from Autronexa.
MTL
MTL3045
Genuine surplus MTL3045 isolator passes 0-20mA to hazardous-area I/P converters and actuators with 800Ω load capability and verified…
MTL
MTL3081
Genuine surplus MTL3081 thermocouple isolator with ±50mV input, non-energy-storing terminals, and optional burnout safety drive. Verified and ready…
News & guides for MTL
Nexans 700 VDC Microgrid: What Changes for Factories and Spares
Nexans has switched part of its own AmpaCity global innovation hub in Lyon, France, onto a 700 V direct-current main distribution…
Orbit 60 PPM (142M8515): What the Module Does and What the 90% Load Warning Means
TL;DR: The Bently Nevada Orbit 60 Protection Processing Module (PPM) is the centralized compute engine of the protection system: it…
Intel Offers Korean AI Chip Firms Custom Design, Packaging and Foundry Routes
Intel used its own Seoul summit to offer Korean AI chip companies custom silicon, advanced packaging and foundry routes. No…
Bently Nevada AnomAlert: Motor Anomaly Detection Without Sensors
TL;DR: The Bently Nevada AnomAlert is a motor anomaly detector that watches a three-phase motor through its voltage and current…
Motion Control Precision: Servo Loops, Fieldbus Jitter, AI
Motion control precision depends on servo loop rates, fieldbus cycle times and jitter, sensor latency and mechanics. AI sits above…
Schneider Electric Product Carbon Footprint Data: What Engineers Can Look Up
TL;DR: Schneider Electric publishes product-level carbon data, but not through a single system. Product pages carry a “total life cycle…
Bently Nevada 3500/06 Weatherproof Housing: Ratings, Purging and Mounting Limits
TL;DR: The weatherproof enclosure for a Bently Nevada 3500 rack is the 3500/06, not the 3500/01 — 3500/01 is the…
Siemens Kärnten Netz Grid Software Contract: Scope and Limits
TL;DR: On 9 November 2026 Siemens announced a six-year software contract with Kärnten Netz GmbH (KNG), the Carinthian distribution system…